Menu 4-1-2 - Signal Inputs
This button is used to call up the list of the digital alarm and signal inputs of the system centre. All
important parameters and the status of the inputs are displayed there. Alarm and signal inputs can be added
using the "New entry" button. Already added digital inputs can be selected and configured using the
corresponding screen or deleted again.
The screen contains the following parameters:
Signal input
Message text
Priority XX
Delay time [Min.] XX
Quiescent current (low-active) X
Signal input
Module
Submodule XX
Input XX
Status XX
1)
 Designations of the supported modules / inputs:
CI 4x00 system centre, internal inputs IN1 / IN2 (terminals A1, A2 / B1, B2)
SIOX1 1. extension module, inputs   1 .. 12
SIOX2 2. extension module, inputs   1 .. 12
SIOX3 3. extension module, inputs   1 .. 12
SIOX4 4. extension module, inputs   1 .. 12
DDC1 1. GLT DDC module  1
DDC2 2. GLT DDC module  2
DDC3 3. GLT DDC module  3
DDC4 4. GLT DDC module  4
Note: GLT = building control and. DDC = Digital Direct Control
Only those SIOX modules and GLT PLC modules are provided for selection that have been configured
accordingly in screen 4-1-1! A description of the functions can be found in chapters
Firmware V7.16.x
Freely editable message text of the digital input
Priority of the signal / alarm input
Delay time of the signal / alarm in minutes
Alarm is signalled if  
- quiescent current = Yes: (signal voltage not 
present, low-active)
- quiescent current = No: (signal voltage is 
present, high-active)
1)
Module 
 to which the message / alarm signal 
is connected
1)
Submodule 
 to which the message / alarm 
signal is applied; this is ONLY visible if
module=DDC1..DDC4 has been selected
1) 
Input 
to which the message / alarm signal is
applied
Current status of the input:
OK = light grey, no signalling
Waiting = yellow: signalling, delay time running,
Message = green: no alarm
Alarm = red: signalling, alarm / message has
been tripped
16.05.2023
Eingabe
max. 19 characters
0..99
0..255
Y/N
SIOX1 ..SIOX4
1..4
1..12
Digital
Vorgabe
-
0
1
Y
-
-
-
-
inputs.
126/183