8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 11.
(Table 11 : Compressor frequency range)
AO*G09LLCA
AO*G12LLCA
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.9.
(Fig.9 : Compressor control at start-up)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
(Frequency)
AO*G09LLCA
AO*G12LLCA
(Time)
AO*G09LLCA
AO*G12LLCA
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.
(Table12 : Limitation of Compressor Frequency)
[ Cooling/ Dry ]
AO*G09LLCA
AO*G12LLCA
[ Heating ]
AO*G09LLCA
AO*G12LLCA
Cooling / Dry
Minimum
Maximum
64rps
18rps
96rps
Time
Time
Frequency
Frequency
56rps
74rps
Time
Time
60sec
100sec
10°C
14°C
Under
Over
Under
25rps
25rps
- 3°C
7°C
Under
Over
Under
25rps
25rps
Heating
Minimum
Maximum
18rps
120rps
Time
Time
Time
Frequency
Frequency
Frequency
87rps
97rps
Time
Time
140sec
200sec
40°C
Over
Under
Over
-------
30rps
14°C
Over
Under
Over
22rps
-------
01-08
Time
6
Frequency
108rps
119rps
Time
Time
6
350sec
410sec
40°C
Under
Over
30rps