3.3.3. Cutting the hole in the wall for the connecting piping
(1) Cut a hole in the wall at the position shown in the following.
(2) Cut the hole so that the outside end is lower (3/16 to 3/8 in (5 to 10 mm)) than the
inside end.
(3) Always align the center of the wall hole. If misaligned, water leakage will occur.
(4) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap
with vinyl tape, and stick the pipe through the hole.
(5) For left piping and right piping, cut the hole a little lower so that drain water will flow
freely.
Wall hook bracket
Lower
3-1/8 (80) dia. hole
3/8 (10)
or more
Attach the wall pipe
Fasten with vinyl
tape
WARNING
If the wall pipe is not used, the
cable interconnecting the indoor
and outdoor units may touch
metal and cause electric leakage.
Wall cap*
3.3.4. Attach the drain hose insulation (30/36 model only)
• Wrap the insulation around the
drain hose, making sure that
there are no gaps.
• Attach the Insulation (drain
hose) to the drain hose.
3.3.5. Forming the drain hose and pipe
Insert drain hose and drain cap securely. Drain should slope down to avoid water leak-
age.
When inserting the drain hose, no other material than water should be applied. Applica-
tion of other material than water will cause deterioration of the hose, and may cause
water leakage.
After you remove a drain hose, be sure to attach the drain cap.
When you secure the piping and drain hose with tape, arrange the drain hose so that it
is at the bottom of the piping.
For drain hose piping in low temperature environment, you need to apply freeze protec-
tion to prevent a frozen drain hose.
After cooling operation is performed in low temperature environment, (when outdoor
temperature under 32°F (0°C),) water in the drain hose could be frozen. Frozen drain
water will block the water flow in the hose, and may cause water leakage at the indoor
unit.
[For (A) Rear piping, (B) Right piping and (C) Bottom piping]
(1) Install the indoor unit piping in
the direction of the wall hole
and bind the drain hose and
pipe together with vinyl tape.
(2) Install the piping so that the
drain hose is at the bottom.
(3) Wrap the pipe of the indoor unit
that visible from the outside
with decorative tape.
(4) For right or bottom outlet
piping, cut off the piping outlet
cutting groove with a hacksaw.
Center mark
Unit: in (mm)
Lower
3-1/8 (80) dia. hole
3/8 (10)
or more
3/16 to
3/8 in
(5 to 10
mm) low
Wall pipe*
* Locally
purchased
(Inside)
Wall
(Outside)
Insulation (drain hose)
(accessories)
Drain hose
CAUTION
Bind with vinyl tape
Pipe (top)
Rear piping
Indoor unit drain hose
Bottom piping
(bottom)
[For (D) Left bottom piping, (E) Left piping and (F) Center piping, (G) Left rear
piping]
Insert the drain hose and drain cap into the drain port, making sure that it comes in con-
tact with the back of the drain port, and then mount it. If the drain hose is not connected
properly, leaking will occur.
(1) Interchange the drain cap and the drain hose.
• For left outlet piping, cut off
the piping outlet cutting groove
with a hacksaw.
• Remove the drain cap by pull-
ing at the projection at the end
of the cap with pliers, etc.
Right side
Installing the drain cap
Use a hexagonal wrench 3/16 in (4 mm) at op-
No gap
posite side to insert the drain cap, till the drain cap
contacts the tip of drain cock.
Hexagonal
Drain cock
wrench
Drain cap
(2) Align the marks on the wall hook bracket and shape the connection pipe.
For left piping and left rear piping, align the marks on the wall hook bracket and
shape the connection pipe.
Wall hook
bracket
Connection
piping
Connection pipe
(liquid pipe)
(3) Bend the connection piping at the bend radius of 4 in (100 mm) or more and install
no more than 2 in (35 mm) from the wall.
3.3.6. Installing the indoor unit
(1) After passing the indoor piping and drain hose through the wall hole, hang the indoor
unit on the hooks at the top and bottom of the wall hook bracket.
After hooking the indoor unit to the top hook, hook the fittings of the indoor unit to the
2 bottom hooks while lowering the unit and pushing it against the wall.
Indoor
unit
(Fitting)
(2) Insert the spacer, etc. between the
indoor unit and the wall hook bracket
and separate the bottom of the indoor
unit from the wall.
CAUTION
Left side
Drain hose
Drain cap
Alignment marks
Connection pipe (gas pipe)
Top hooks
Wall hook
bracket
Bottom hooks
Indoor unit
Spacer
Wall hook bracket