Outlines And Dimensions - Mitsubishi Electric PLFY-P20VBM-E.UK Technical & Service Manual

Table of Contents

Advertisement

6

OUTLINES AND DIMENSIONS

PLFY-P20/25/32/40/50/63/80/100/125VBM-E.UK
PLFY-P32/40/50/63/80VBM-E
PLFY-P32/40/50/63/80/100/125VBM-ER2.UK
PLFY-P32/40/50/63/80/100/125VBM-ER3.UK
20~45
Fresh air
Suspension bolt pitch
160
intake hole
Indoor/outdoor unit connecting
terminal block
Power supply
Branch duct hole
terminal block
Suspension bolt
187.5
M10 or W3/8
1
60
284
2
*
*
Suspension bolt
lower edge
Power supply wire,
*
Indoor unit/Outdoor unit
connecting wire entry
Control wire entry
M
Air intake
grille
M
Corner pocket
Indoor unit
Ceiling
Grille
1500 mm
Obstacle
or more
OCH413E
.UK
1
Ceiling hole
860~910
20~45
810
For MA-Remote controller
terminal block
160
840
Drain pipe
connected to VP-25
377
*
*
Ceiling
Grille
597
Air intake hole
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
M
Auto vane
(Air outlet)
M
Vane motor
500
83
36
Air outlet hole
950
Indoor unit
3000 mm or
more
1800 mm or more
from floor
For high
attachment
Floor
Detail connecting of branch duct(Both aspects)
Branch duct hole
Burring hole pitch
(
Connected the attached
flexible pipe or socket.
Keep approximately
10 to 15 mm space
between unit ceiling
and ceiling slab.
*
*
In case of standard grille : PLP-6BA/PLP-6BAMD
In case of auto-grille : PLP-6BAJ
In case of wireless remote controller : PLP-6BALM
Emergency operation switch<Cooling>
and Emergency Up/Down switch<Up>
Emergency operation
switch<Heating>and
Emergency Up/Down switch<Down>
DEFROST/STAND BY lamp
Receiver
Operation lamp
Note 1. Please choose the grille from a standard grille, auto-grille.
2. As for drain pipe, please use VP-25 (O.D. [32 PVC TUBE).
Drain pump is included.
Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional
multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions * marked on the figure.
3) The optional high efficiency filter must be used jointly with optional multi-functional
casement.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/water dew.)
8. As for necessary installation/service space, please refer to the left figure.
Accessory ··· Drain socket (I.D. 32)
Models
PLFY-P20, 25, 32, 40, 50VBM-E
Refrigerant pipe···[6.35
Flared connection···1/4 inch
PLFY-P63,80VBM-E
Refrigerant pipe···[9.52
Flared connection···3/8 inch
PLFY-P100,125VBM-E
22
90
100
100
90
Cut out hole
350
[175
14-[2.8
Burring hole
[150
Cut out hole
Detail drawing of fresh air intake hole
Burring hole
3-[2.8
)
*
Auto-grille
Air intake grille up/down distance
L.L Filter
Air intake grille
1
2
Refrigerant pipe ···[12.7
Flared connection···1/2 inch
241 258
Refrigerant pipe···[15.88
Flared connection···5/8 inch
281
Unit: mm
*
Burring hole pitch
[125
Cut out hole
[100
Ceiling
Ceiling
A
B
C
D
E
80
74
400
85
77
298
440