Lennox ELXA Series Unit Information page 18

Air handler units
Table of Contents

Advertisement

OPTIONAL ELECTRIC HEAT DATA - EL240XA
No.
Electric Heat
of
Size
Steps
20 kW
1
1
1
1
30 kW
2
2
1
1
40 kW
2
2
1
1
50 kW
2
2
2
2
Electric heater capacity only - does not include additional blower motor heat capacity.
1
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
2
Volts
kW
Btuh
1
Input
Input
Output
208
14.8
50,600
220
16.5
56,500
230
18.1
61,800
240
19.7
67,300
440
16.8
57,500
460
18.4
62,900
480
20
68,300
550
16.7
57,300
575
18.4
62,600
600
20
68,300
208
22.5
76,900
220
25.2
86,100
230
27.6
94,100
240
30
102,500
440
25.2
86,100
460
27.6
94,100
480
30
102,500
550
25.2
86,100
575
27.6
94,200
600
30
102,500
208
29.3
100,000
220
32.8
112,000
230
35.8
122,300
240
39
133,200
440
32.8
112,000
460
35.9
122,400
480
39
133,200
550
33.6
114,800
575
36.7
125,500
600
40
136,600
208
36.1
123,200
220
40.3
137,700
230
44.1
150,600
240
48
163,900
440
42
143,400
460
45.9
156,700
480
50
170,800
550
42
143,500
575
45.9
156,800
600
50
170,800
Total Unit + Electric Heat
2
Minimum Circuit
Ampacity
5 hp
7.5 hp
73
82
81
90
40
44
32
36
99
109
112
121
55
59
44
48
123
132
139
148
69
73
56
60
121
131
137
146
81
91
69
79
Page 18
Total Unit + Electric Heat
Maximum Overcurrent
Protection
5 hp
7.5 hp
80
90
90
90
40
45
35
40
100
110
125
125
60
60
45
50
125
150
150
150
70
80
60
60
125
150
150
150
90
100
70
80

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

El072xassEl090xasdEl120xasdEl150xasdEl180xasdEl240xasd

Table of Contents