13. Installation
AF50MS3MCEENHC+AF50MS3MCEEXHC, AF50MV3MCEENHC+AF50MV3MCEEXHC
Electrical work
Wiring work must be done by the certified expert.
f Wiring work should be performed in accordance with related laws such as technical specification on electric
f
installation or installation guide.
f You must install exclusive power supply.
f
- If you use multi-outlet, there is a risk of electric shock or fire.
- After initial installation, customer is responsible for re-installation fee.
f Please install a circuit breaker. (Rated current sensitivity over 30 mA)
f
- After initial installation, customer is responsible for re-installation fee.
f Tightening torque of the screws on the terminal block should be within the rated range and make sure that they don't
f
get loosened.
f Please connect ground wire.
f
❋ Please install the power wire with it length shorter than 50 m. If the length of the power wire exceeds 50 m inevitably,
product may not work or wire could get damaged. Therefore please contact the system expert.
Power specification
Model name
Power supply
Power consumption
Operating current
Capacity of circuit breaker
Thickness of ground wire
Indoor and Outdoor unit power wire
Indoor and Outdoor unit communication wire
Power wire
Product
36
Indoor unit
Outdoor unit
Product
T1
Cooling
T3
Heating
-
T1
Cooling
T3
Heating
-
Product
A
mm²
mm²
mm²
Type
Below 20 m
mm²
20 m or over
mm²
AF50MS3MCEENHC
AF50MS3MCEEXHC
3 phase 4 wires 380-415V, 50Hz
4320 W
-
4500 W
6.8 A
-
6.7 A
At least 4.0 or more
At least 1.5 or more
0.75
At least equal to H05RN-F
4.0(Should be purchased separately)
6.0(Should be purchased separately)
AF50MV3MCEENHC
AF50MV3MCEEXHC
4320 W
-
-
6.8 A
-
-
20