Ionization Current; Firing Head Disassembly - Ecoflam BLU 15000.1 Manual

Progressive gas burners
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 10
420010310700 BLU 15000.1 - 20000.1 PR TS
EN
The ionization current is checked by inserting a
microammeter with an end of scale of 50 µA (d.c.)
in series with the ionization probe.
A faulty position of the electrode can lead to a
reduction in the ionization current and cause a
safety cut-out of the burner due to a flame detec-
tion failure. In this case, check the position of the
electrode, its electric connection and the earthing
of the burner. The ionization current is normally > 20 µA.
REMOVING THE BLAST TUBE

IONIZATION CURRENT

16
min. 6 A
Microammeter
Microamperometro
fondo scala 50 A
50 μA end of scale
FIRING HEAD
DISASSEMBLY
24
LANDIS LFL1.622
LANDIS LFL1.333