5
|
Operation

5.7.3 Scheduled mode

5.7.4 Scheduled + reheat mode

User reference guide
32
INFORMATION
When the DHW tank mode is reheat, the risk for capacity shortage and comfort
problem is significant. In case of frequent reheat operation, space heating/cooling
function is regularly interrupted.
In scheduled mode, the DHW  tank produces hot water corresponding to a
schedule. The best time to allow the tank to produce hot water is at night, because
the space heating demand is lower.
Example:
T t
60°C
50°C
40°C
15°C
00:00
T
DHW tank temperature
t
t Time
Initially, the DHW  tank temperature is the same as the temperature of the
domestic water entering the DHW tank (example: 15°C).
At 00:00 the DHW  tank is programmed to heat up the water to a preset value
(example: Comfort = 60°C).
During the morning, you consume hot water and the DHW  tank temperature
decreases.
At 14:00 the DHW  tank is programmed to heat up the water to a preset value
(example: Eco = 50°C). Hot water is available again.
During the afternoon and evening, you consume hot water again and the
DHW tank temperature decreases again.
At 00:00 the next day, the cycle repeats.
In scheduled + reheat mode, the domestic hot water control is the same as in
scheduled mode. However, when the DHW tank temperature drops below a preset
value (=reheat tank temperature – hysteresis value; example: 35°C), the DHW tank
heats up until it reaches the reheat set point (example: 45°C). This ensures that a
minimum amount of hot water is available at all times.
Example:
T t
60°C
50°C
45°C
35°C
15°C
00:00
T
Domestic hot water tank temperature
t
t Time
1
2
4
3
5
07:00
14:00
21:00
1
2
3
07:00
14:00
21:00
t
4
5
t
ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708480-1 – 2023.05