Technical Data; Installation - Viking VK520 Manual

Esfr upright sprinkler

Advertisement

Sprinkler 121b
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Ordering Information: (Also refer to the current Viking price list.)
Order ESFR Upright Sprinkler VK520 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for
the temperature rating to sprinkler base part number.
Finish Suffix: Brass = A
Temperature Suffix: 165 °F (74 °C) = C, 205 °F (96 °C) = E
For example, sprinkler 10625 with a Brass finish and a 165 °F (74 °C) temperature rating = Part No. 10625AC.
Available Finishes And Temperature ratings:
Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrench: Part No. 05118CW/B
Sprinkler Cabinet:
Six-head capacity: Part No. 03985A (available since 1977)

4. INSTALLATION

WArNINg: Viking sprinklers are manufactured and tested to meet rigid requirements of the approving agency. The sprinklers are
designed to be installed in accordance with recognized installation standards. System design must be based on ESFR design
guidelines described in the latest edition of Viking technical data, applicable FM Global Loss Prevention Data Sheets, the latest
NFPA Standards, the Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and stand-
ards whenever applicable. Deviation from the standards or any alteration to the sprinkler after it leaves the factory including, but not
limited to: painting, plating, coating, or modification, may render the sprinkler inoperative and will automatically nullify the approval
and any guarantee made by The Viking Corporation.
A. Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install
sprinklers that have been dropped or damaged in any way or exposed to temperatures in excess of the maximum ambient tempera-
ture allowed. Such sprinklers should be destroyed immediately. NOTE: Wet pipe systems must be provided with adequate heat.
B. The sprinklers must be installed after the piping is in place to prevent mechanical damage. Before installing, be sure to have the
appropriate sprinkler model and style, with the correct orifice size, temperature rating, and response characteristics. NOTE: No
sprig is required for sprinkler pipe sizes up to and including 3" (76.2 mm) nominal O.D.
C. With the sprinkler contained in the plastic protective cap, apply a small amount of pipe-joint compound or tape to the male
threads only, while taking care not to allow a build-up of compound in the sprinkler orifice.
D. use ONLY sprinkler wrench 05118CW/B (shown in Figure 1) for installing ESFr Sprinkler Vk520! With the sprinkler
contained in the protective cap, install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler
wrench flats only, while taking care not to damage the sprinkler operating parts.
DO NOT use any other type of wrench, as this could damage the unit.
DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting.
DO NOT exceed 50 ft. lbs. of torque (hand tight, plus approximately two full turns with the wrench) to install these sprinklers.
Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.
E. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the Installation
Standards. Make sure the sprinkler has been properly tightened. If a thread leak occurs, normally the unit must be removed, new
pipe-joint compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal is damaged, the sealing
compound or tape is washed out of the joint. Immediately replace any damaged units, using the special sprinkler wrench only.
TABLE 1: AVAILABLE SPrINkLEr TEMPErATurE rATINgS AND FINISHES
Sprinkler Temperature
Classification
Ordinary
Intermediate
Sprinkler Finish: Brass
The sprinkler temperature rating is stamped on the deflector.
1
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
2
Refer to specific installation standards.

TECHNICAL DATA

Sprinkler Nominal
Temperature rating
1
165 °F (74 °C)
205 °F (96 °C)
Footnotes
ESFr uPrIgHT SPrINkLEr
SIN Vk520 (k14.0)
Maximum Ambient
Ceiling Temperature
2
100 °F (38 °C)
150 °F (65 °C)
April 1, 2011
Frame Paint
Color
None
White

Advertisement

loading

This manual is also suitable for:

10625