4.1

Technical data

4.1.1

Interfaces

USB host
Product name
Type
Number
Device category
Application
Data rate
Max. current
Ethernet
Product name
Type
Number
Protocol
Application
Transfer rate
Connecting cable
Cable length
RS485 (serial interface)
Product name
Type
Number
Application
Protocol
Data format
Transfer rate
USB
A (socket)
2
Mass Storage Class, Communications Device Class – Ethernet Con-
trol Module
Connecting a USB flash drive or a USB to Ethernet converter
Low Speed, Full Speed, Hi-Speed
500 mA per interface
LAN1, LAN2, LAN3 (optional)
RJ45
1
TCP, IPv4, HTTP(S)
Via CODESYS as an option: Modbus TCP, PROFINET IO controller,
EtherCAT master, OPC UA server, BACnet/IP
Communication with:
- PC (setup program, web browser)
- email server
- Modbus TCP master/slave
- PROFINET IO device
- EtherCAT slave
- OPC UA client
- BACnet/IP server/client
- JUMO system bus via JUMO variTRON router modules (LAN1 only)
10 Mbit/s, 100 Mbit/s (EtherCAT: 100 Mbit/s)
Network cable, at least CAT5e (S/FTP)
Up to 100 m
COM
D-Sub 9-pole
1
Fieldbus applications, communication via modem with a PC or with
an email server
Via CODESYS: Modbus RTU master/slave
8/1/n, 8/1/e, 8/1/o
9600 Bd, 19200 Bd, 38400 Bd, 115200 Bd