Download Print this page
Hitachi air Home 400 Installation Manual

Hitachi air Home 400 Installation Manual

Split unit air conditioner
Hide thumbs Also See for air Home 400:

Advertisement

Quick Links

INSTALLATION
Please request your sales agent or qualifi ed technician to install your unit. Water leakage,
MANUAL
short circuit or fi re may occur if you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of
installation. Improper installation may cause water leakage, electric shock and fi re.
Make sure that the units are mounted at locations which are able to provide full support to
Home
the weight of the units. If not, the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in
the installation manual when dealing with the electrical work. Use cables which are offi cially
approved in your country. Be sure to use the specifi ed circuit. A short circuit and fi re may
occur due to the use of low quality wire or improper work.
Be sure to use the specifi ed cables for connecting the indoor and outdoor units. Please
ensure that the connections are tight after the conductors of the wire are inserted into the
terminals to prevent the external force is being applied to the connection section of the
terminal base. Improper insertion and loose contact may cause over-heating and fi re.
SPLIT UNIT AIR CONDITIONER
Please use the specifi ed components for installation work. Otherwise, the units may collapse
or water leakage, electric shock, fi re or stronger vibration may occur.
INDOOR UNIT
Be sure to use the specifi ed piping set for R32. Otherwise, this may result in broken copper
RAK-DJ60PHAT
pipes or faults.
When installing or transferring an air conditioner to another location, make sure that air
other than the specifi ed refrigerant(R32) does not enter the refrigeration cycle. If other air
EN INSTRUCTION MANUAL
should enter, the pressure level of the refrigeration cycle may increase abnormally which
could result in a rupture and injury.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes
FOR SERVICE
into contact with fi re, a poisonous gas may occur.
PERSONNEL ONLY
After completion of installation work, check to make sure that there is no refrigeration gas
leakage. If the refrigerant gas leaks into the room, coming into contact with fi re in the fan-
driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifi cations to the air conditioner may be dangerous. If a breakdown occurs
please call a qualifi ed air conditioner technician or electrician. Improper repairs may result
in water leakage, electric shock and fi re, etc.
Be sure to connect the earth line from the power supply wire to the outdoor unit and between
Carefully read through the procedures of
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting
proper installation before starting installation
work.
rod or the earth line of the telephone unit. Improper earthing may cause electric shocks.
The sales agent should inform customers
When fi nishing the refrigerant collection (pumping down), stop the compressor and then
regarding the correct operation of installation.
remove the coolant pipe. If you remove the refrigerant pipe while the compressor is operating
and the service valve is released, air is sucked and a pressure in the freezing cycle system
will build up steeply, causing an explosion or injury.
When installing the unit, be sure to install the refrigerant pipe before starting the compressor.
Tools Needed For Installation Work
If the refrigerant pipe is not installed and the compressor is operated with the service
(Mark
is exclusive use tool for R32)
valve released, air is sucked and the pressure level of the refrigeration cycle may increase
+ –
Screwdriver
Measuring Tape
abnormally which could result in a rupture and injury.
Knife
Saw
ø 65mm Power Drill
The electric cables should neither be reworked nor added. Make sure to use an exclusive
Hexagonal Wrench Key (
4mm)
circuit breaker. Otherwise fi re or electric shock might occur by connection failure, isolation
Wrench (14,17,19,22mm)
failure or over current.
Gas Leakage Detector
Pipe Cutter
Make sure to connect cables to terminal properly and terminal cover should close fi rmly.
Putty
Vinyl Tape
Pliers
Otherwise, over heating at terminal contact, fi re or electric shock might occur.
Flare Tool
Vacuum Pump Adaptor
Make sure that there is no dust on any connected points of electric cables and fi x fi rmly.
Manifold Valve
Charge Hose
Otherwise, fi re or electric shock might occur.
Vacuum Pump
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
!
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
CAUTION ......... Improper installation may result in serious consequence.
Make sure to connect earth wire.
This sign in the fi gures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation
and maintenance of the unit as described in the user's guide. Ask a customer to keep this installation manual
together with the instruction manual.
< IA2275: A >
1
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
The draining of the water container inside the indoor unit can be done from the left. Therefore the hanger
must be fi xed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water
may overfl ow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
660mm
145mm
65
105mm
950mm
Level
Screw for Hanger
Line
Weight
Wall hole
Procedures of Installation and Precautions
Procedures to fi x the hanger.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Wall
1
Hanger
Plug
Screw
2
(Procure
locally)
Wall
32mm
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on wall which
is slightly tilted towards the outdoor
side. Drill the wall at a small angle.
Cut the protection pipe according
to the wall thickness.
Seal with
Empty gap in the sleeve of protection
putty
pipe should be completely sealed
with putty to avoid dripping of rain
water into the room.
Please ensure smooth fl ow of water
when installing the drain hose.
Protection
Improper installing may wet your
pipe
furniture.
An IEC approved power cord should
be used. Power cord type: NYM.
>
< IA2275: A
WARNING
!
!
CAUTION
145mm
Drain Hose
67mm
Screw the hanger at the positions
Hanger
possibly near the upper and lower
hooks where the indoor unit is
hung. Use 4 or more screws to
fi x the hanger.
3. Fix the hanger on wall
with 4.1 x 32 screw
(As shown in fi gure below)
Ceiling
WARNING
!
Indoor
Outdoor
Be sure that the wire is not
2-5mm
in contact with any metal
in the wall. Please use
Seal with
the protection pipe as wire
putty
passing through the hollow
part of the wall so as to
prevent the possibility of
damaged by mouse.
Unless it seals completely,
WALL
any air with high humidity
Sleeve of
fl ows from outdoor and dew
protection pipe
may drop.
The Choice of Mounting Site
(Please note the following matters and obtain permission from customer before installation).
!
CAUTION
A circuit breaker must be installed in the house distribution
box for the direct connected power supply cables to the
outdoor unit. In case of other installations a main switch
with a contact gap or more than 3mm has to be installed.
Without a circuit breaker, the danger of electric shock
exists..
Do not install the unit near a location where
there is fl ammable gas. The outdoor unit may
catch fi re if fl ammable gas leaks around it.
Please ensure smooth fl ow of water when installing the
drain hose. Improper installing may wet your furniture.
An IEC approved power cord should be used. Power cord
type: NYM.
The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.
No nearby heat source and no obstruction near the air outlet is allowed.
The clearance distances from top, right and left are specifi ed in fi gure below.
The location must be convenient for water drainage and pipe connection with the Outdoor unit.
No nearby leakage risk of fl ammable gas, and no nearby source of vapor or oil smoke.
To avoid interference from noise, please place the unit and its remote controller at least 1m from the radio and television.
To avoid any error in signal transmission from the remote controller, please put the controller far away from high-frequency
machines and high-power wireless systems.
The installation height should be at least 2300 mm or more from the fl oor.
The distance from the air outlet to the fi re alarm must be at least 1500mm and there must be no fi re alarm in the front
direction of the indoor unit.
Figure showing the Installation of Indoor Unit.
above 50mm
1
above 100mm
Be sure to
completely
seal any gap
with putty.
above 100mm
2300 or more
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator
is insufficient, please use
6
commercial products.)
4
5
3
2
Installation of the Indoor Unit
Cutting Low Cover bush
While installing the pipe from the right, left or bottom
side, use a knife to cut openings as shown in fi gure.
Then smoothen the edges of openings with a fi le.
PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
1
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
Installation
Insert the pipe through the wall hole.
1 The upper part of the Indoor unit is hanged on the hanger.
2 The projection at the lower part of the Indoor unit is hooked
onto the hanger
1
Hanger
Lift the body of
Refrigerating
the unit upwards
pipe
and then force it
downwards.
Protection Pipe
Connecting Cord
Drain Hose
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
2
Preparation
Changed of Drain Hose and Installation Procedures
Exchange the location of drain hose and drain cap while installing the pipe from the left side as shown in below.
Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain
cap).
Drain cap
Drain Hose
Remove low cover.
Insert drain cap up to the location securely till the cap stops.
Drain hole
!
CAUTION
The rubber strap used for fi xing the insulator should not be tied with great force.
Otherwise, this will damage heat insulation and causes water condensation..
Please pull the lower part of the indoor unit outwards to check if the unit is hooked
onto the hanger. Improper installation may cause vibration and noise.
Transform the piping while holding down the lower portion of pipe-support by
hand.
WARNING
This symbol shows that this equipment uses a fl ammable
refrigerant.
If the refrigerant is leaked, together with an external ignition
source, there is a possibility of ignition.
CAUTION
This symbol shows that the Operation Instructions should
be read carefully.
CAUTION
This symbol shows that a service personnel should be
handling this equipment with reference to the Installation
Manual.
CAUTION
This symbol shows that there is information included in
the Operation Manual and/or Installation Manual.
!
WARNING
!
CAUTION
2
Names of Indoor Components
No.
Item
Hanger
1
Screw for Hanger
Direction of Piping
2
Backward piping from left
AAA size Battery
3
Remote Controller
4
Connection
There are 6 directions
Screw for Remote
allowed, namely,
Controller Holder
backward piping,
5
backward piping from left,
horizontally piping from
right, horizontally piping
Air purifying fi lter
from left, vertically down
6
from right, vertically down
from left.
Openings
Openings
Connecting cords, pipe
and drain hose must
be laid together with
Vinyl tape.
Wall hole
Pipe
Drain hose
Cable
1
Hanger
1
Drain layout of backward piping
2
Projection
!
CAUTION
Insuffi cient insert may result in water leakage.
Push the pipe deeply until the insulating section
of the drain hose end gets over the rib at the
indoor unit side.
Rubber strap tied
Pipe
with great force
Transform after
Pipe support
bending downward
Qty
1
6
2
1
2
2

Advertisement

loading

Summary of Contents for Hitachi air Home 400

  • Page 1 The Choice of Mounting Site (Please note the following matters and obtain permission from customer before installation). WARNING CAUTION INSTALLATION WARNING This symbol shows that this equipment uses a fl ammable A circuit breaker must be installed in the house distribution ●...
  • Page 2 INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES THE CONNECTION OF REFRIGERATING PIPE DURING THE Outer Torque N·m The refrigerating pipe should be adjusted to fi t into the hole on the wall and dia.of pipe (kgf · INSTALLATION OF INDOOR UNIT ●...

This manual is also suitable for:

Rak-dj60phat