resistance for each battery. A wide variation in circuit resistance can
result in unbalanced discharging and charging of cells. As a
consequence this can produce unequal float voltages of the
connected cells and individual strings can sustain a loss of
performance and capacity, resulting in higher loads on the other
parallel strings with lower cable (circuit) resistance.