Functions
• Quick exchange of a device in case of a failure without new configuration
• Applying a standard configuration
• Backup of a device configuration on portable hardware.
An EDS500 500FSD20 modem detects the configuration stick automatically during operation. If
the configuration stick is plugged into the device at power on then the configuration is loaded from
the stick and copied to the internal configuration memory. A previously saved startup-config gets
overwritten.
2.4.1

Show configurations

Commands to show the configurations
< s h o w c o n f i g >
< s h o w r u n n i n g - c o n f i g >
< s h o w s t a r t u p - c o n f i g >
< s h o w s t i c k - c o n f i g >
2.4.2

Modifying start-up configuration

Commands to modify the start-up configuration
< w r i t e >
< w r i t e m e m o r y >
< c o p y r u n n i n g - c o n f i g s t a r t u p - c o n f i g >
< c o p y r u n n i n g - c o n f i g s t i c k - c o n f i g >
< c l e a r s t a r t u p - c o n f i g >
< c l e a r s t i c k - c o n f i g >
< s e t c o n f i g - s t i c k r e a d - o n l y >
< s e t c o n f i g - s t i c k n o r e a d - o n l y >
If a configuration is copied to the internal startup-config then it is also copied to the configuration
stick if that is plugged in and not write-protected.
An empty configuration is not necessarily identical with the default configuration. The default
configuration represents the state at the time of shipping and eases the access to the device
(Chapter 2.4.4, "Default configuration and reset of a device").
2.4.3

Power-up, configuration stick and modifications during runtime

At start-up there is no running-config yet. The device internal start up configuration is loaded
and the included commands are executed. The result is the initial running-config that is identical
to the startup-config. If during operation further configuration commands are executed then the
running-config is modified. If the configuration stick is plugged in during operation then the stored
configuration can be accessed. There is no automatic transfer of the configuration.
The data of the configuration stick is not used before a restart of the device and then the data is
copied to the startup-configuration.