Redlion Graphite GMUIN4 Installation Manual

Redlion Graphite GMUIN4 Installation Manual

Universal input module

Advertisement

Quick Links

Model GMUIN4 - Graphite® Universal
Installation Guide
U L
FOR USE IN HAZARDOUS LOCATIONS:
C C
US
US
R
Class I, Division 2, Groups A, B, C, and D
LISTED
T4
IND.CONT. EQ.
E302106
E317425
GENERAL DESCRIPTION
The model GMUIN4 is a 16-bit analog input module designed for
use with the Graphite products. The module provides 4 isolated
universal analog inputs as a means of signal measurement for data-
acquisition. The GMUIN4 accepts a wide range of thermocouples
and RTDs, as well as 0/4-20 mA and 0-10 V process signals. The
modules connect and communicate via proprietary USB connection
to the various Graphite devices. The Graphite devices, equipped
with serial ports as well as an Ethernet port(s), allows the system to
share data with PCs, PLCs, and SCADA systems. The maximum
number of modules varies for each Graphite device, see specific
models for details.
Once programmed, the module will continue to operate
independent of the Graphite device as long as power is applied.
Remove power from the host device before installing or replacing
any modules.
CONFIGURATION
The Graphite is configured with Windows
DIMENSIONS In inches (mm)
2.97 (76)
4.65
(118)
Input Module
®
®
compatible Crimson
1.25 (32)
1
z Dedicated 4 universal input module for the Graphite
products
z Accepts thermocouples, RTDs, 0/4-20 mA and 0-10 V signal
inputs
z Offers complete isolation; inputs, power and core
z Ideal for data-acquisition applications
software. The software is an easy to use, graphical interface which
provides a means of configuration and commissioning of new
systems, as well as routine module re-calibration.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that
appear in this document or on equipment must be observed to
ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not specified.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
WARNING - EXPLOSION HAZARD - Do not disconnect
equipment unless power has been switched off or area is
known to be non-hazardous.
WARNING - EXPLOSION HAZARD - Substitution of
components may impair suitability for Class I, Division 2
ORDERING INFORMATION
DESCRIPTION
Graphite Module, 4 Universal Inputs
A listing of the entire Graphite family of products and accessories
can be found at www.redlion.net.
Install - GMUIN4-K
Drawing No. LP0923
Revised 04/2023
II 3 G Ex nA IIC T4 Gc
-40°C≤T
≤75°C
AMB
DEMKO 14 ATEX 1387X
IECEx UL 15.0035X
UL22UKEX2574X
PART NUMBER
GMUIN400

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Graphite GMUIN4 and is the answer not in the manual?

Questions and answers

Summary of Contents for Redlion Graphite GMUIN4

  • Page 1 WARNING - EXPLOSION HAZARD - Substitution of components may impair suitability for Class I, Division 2 4.65 ORDERING INFORMATION (118) DESCRIPTION PART NUMBER Graphite Module, 4 Universal Inputs GMUIN400 A listing of the entire Graphite family of products and accessories can be found at www.redlion.net.
  • Page 2: Specifications

    (+) Violet (+) Brown range among equipment used in your Graphite system. -328 to +1346°F (-) Red (-) Blue Consult the user manual or www.redlion.net/OpTemp -200 to +760°C (+) White (+) Yellow further details. -328 to +1400°F (-) Red (-) Blue Storage Temperature Range: -40 to +85 °C T...
  • Page 3: Emc Installation Guidelines

    4. Long cable runs are more susceptible to EMI pickup than Visit http:/ /www.redlion.net/emi for more information on EMI short cable runs. guidelines, Safety and CE issues as they relate to Red Lion 5.
  • Page 4: Hardware Installation

    Drawing No. LP0923 Revised 04/2023 HARDWARE INSTALLATION The physical order of all installed modules must match the modules order in Crimson. Torque screws to 6.0 pound-force inch [96 ounce-force inch] (0.68 Nm). WARNING: Disconnect all power to the unit before installing or removing modules.
  • Page 5: Firmware Upgrade

    Module is controlling properly, but has lost Flashing Green Lion’s technical support. communication with the Host. Support: support.redlion.net Website: www.redlion.net AL1, AL2, AL3, AL4 – Alarm LEDs Inside US: +1 (877) 432-9908 The Alarm LEDs indicates the presence of an input fault Outside US: +1 (717) 767-6511 condition.
  • Page 6 Drawing No. LP0923 Revised 04/2023 This page intentionally left blank.
  • Page 7 Revised 04/2023 Drawing No. LP0923 This page intentionally left blank.
  • Page 8: Limited Warranty

    (a) Red Lion Controls Inc. (the “Company”) warrants that all Products shall be free from defects in material and workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at www.redlion.net ) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY;...

This manual is also suitable for:

Graphite gmuin400

Table of Contents