PAGE 1
HE-XE102
PRELIMINARY
1
SPECIFICATIONS
HE-XE102 Specifications
Digital DC Inputs
Inputs per Module
Commons per Module
Input Voltage Range
Absolute Max. Voltage
Input Impedance
Input Current
Upper Threshold
Lower Threshold
Max Upper Threshold
Min Lower Threshold
OFF to ON Response
ON to OFF Response
HSC Max. Switching Rate
Digital Relay Outputs
Outputs per Module
Commons per Module
Max. Output Current
Max. Total Current
Max. Output Voltage
Max. Switched Power
Contact Isolation to XLE ground
Max. Voltage Drop at Rated Current
Expected Life
Max. Switching Rate
Type
Response Time
Analog Inputs, Medium Resolution
Number of Channels
Input Ranges
Safe input voltage range
Input Impedance
(Clamped @ -0.5 VDC to 12 VDC)
Nominal Resolution
%AI full scale
Max. Over-Current
Conversion Speed
Max. Error at 25°C
Additional error for temperatures
other than 25°C
Filtering
General Specifications
Required Power
(Steady State)
Required Power
(Inrush)
Primary Power
Range
Relative Humidity
Operating
Temperature
Terminal Type
Screw Type, 5 mm Removable
Weight
CE
See Compliance Table at
http://www.heapg.com/Support/compliance.htm
UL
4 Analog Inputs (Medium Resolution)
12 including 4 configurable
HSC inputs
1
12 VDC / 24 VDC
35 VDC Max.
10 kΩ
Positive
Negative
Logic
Logic
0.8 mA
-1.6 mA
0.3 mA
-2.1 mA
8 VDC
3 VDC
1 ms
1 ms
10 kHz
6 relay
6
5 A at 250 VAC, resistive
5 A continuous
275 VAC , 30 VDC
150 W, 1250 VA
1000 VAC
0.5 V
No load: 5,000,000
Rated load: 100,000
300 CPM at no load
20 CPM at rated load
Mechanical Contact
One update per ladder
scan plus 10 ms
4
0 - 10 VDC
0 – 20 mA
4 – 20 mA
-0.5 V to +12V
Current Mode:
100 Ω
Voltage Mode:
500 k Ω
10 Bits
32,000 counts
35 mA
All channels converted
once per ladder scan
TBD
TBD
160 Hz hash (noise) filter
1-128 scan digital running
average filter
130 mA @ 24 VDC
30 A for 1 ms @ 24 VDC
10 – 30 VDC
5 to 95% Non-condensing
0° to 50° Celsius
12 oz. (340.19 g)
15 MAY 2006
XLE OCS Model: HE-XE102
12 Digital DC Inputs
6 Digital Relay Outputs
2
Panel Cut-Out and Dimensions
Refer to XLE User Manual (MAN0805) for panel box information and a handy checklist of requirements.
Note: The tolerance to meet NEMA standards is ± 0.005" (0.1 mm).
3.622 [92mm]
001XLE002
3
Ports / Connectors / Cables
Note: The case of the XLE is black, but for clarity, it is shown in a lighter gray color.
To Remove Back Cover:
Unscrew 4 screws located on
the back of the unit.
Lift lid.
CAUTION: Do not overtighten
screws when screwing the lid
back on.
I/O Jumpers: (Not Shown)
I/O Jumpers (JP) are located
internally. To access, remove
back cover of unit.
The I/O Jumpers, External
Jumpers and Connectors (J1
/ J2) are described in the
of this document.
Memory Slot:
Uses Removable Memory for
data logging, screen captures,
program loading and recipes.
Horner Part No.: HE-MC1
Serial Communications:
MJ1: Use for Cscape
programming and Application-
Defined Communications.
MJ2: Use for Application-
Defined Communications
Pin
8
8
7
6
5
1
4
3
2
1
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
MJ1 Pins
MJ2 Pins
Signal
Direction
Signal
TXD
OUT
TXD
RXD
IN
RXD
0 V
Ground
0 V
NC
No Connect
NC
CTS
OUT
TX-
RTS
IN
TX+
RX- / TX-
IN / OUT
RX-
RX+ / TX+
IN / OUT
RX+
MAN0808-01
Specifications / Installation
Want More Information?
To download the XLE User
Manual (MAN0805), refer to
Technical Support in this
document.
CAN Connector
Use the CAN Connector when
using CsCAN network.
Direction
OUT
IN
Ground
No Connect
OUT
OUT
IN
IN
Need help?
Do you have a question about the HE-XE102 and is the answer not in the manual?
Questions and answers