Trane CyberRow DX Installation, Operation And Maintenance Manual page 53

Row-based precision air conditioners
Table of Contents

Advertisement

Group Confi g
Unit ACTIVE
Total in Network
Min Number Active
Enb lead override
Lead Unit
Factory>Group> Group Config (Screen 1)
(See table below.)
Display
Description
Assign the duty of
the A/C unit within
the group.
Unit
The duty must be
assigned for each
A/C unit at its local
display terminal.
Enter the total
Total in Network
number of A/C
units in the group.
Enter the total
Min Number
number of active
Active
A/C units in the
group.
If set to yes, you
may manually
Enb lead override
assign the lead
unit in the following
field.
Identifies which A/
C unit controller is
currently the lead
unit in the group. If
Lead Unit
Enb lead override
is set to yes, you
may select which
unit is lead.
Group Rotation
Force Rotation
Number of Days
Hour of Day
Cur lead 1 Rot Unit 0
Next lead 0
AH-SVX015A-EN
1
1
No
1
Variables
Default
0= Out of Service
1 = Active
2= Standby
3= Assist
1
4= Active_No_Rot
5= Standby_No_Rot
6= Assist_No_Rot
0 to 9
1
0 to 9
1
0= No
No
1= Yes
1 to 8
1
Off
00
00
Value 0
Factory>Group>Group Rotation (Screen 2)
From this screen you may set the schedule to rotate operation
of the A/C units to promote equal run times.
Display
Description
This field only
appears on the
Lead controller. If
you select On and
press Enter it
initiates a manual
rotation cycle to
rotate duty
Force Rotation
between active
and standby units.
It also rotates the
role of Lead
controller. The
field will disappear
after the role of
Lead is rotated to
the next A/C unit.
Enter the number
of days between
Number of Days
rotating active
units.
Enter the hour of
Hour of Day
day for unit
rotation to occur.
Identifies which A/
C unit controller is
Cur Lead
currently the lead
unit in the group.
Identifies which A/
C unit controller is
Next lead
designated to be
the next lead unit.
Identifies which A/
C unit is
Rot Unit
designated to be
the next unit to
rotate duty.
Identifies the duty
of the A/C unit by
displaying the
variable number
assigned in
Value
Factory>Group
screen
1 (0=Out of
Service, 1=Active,
2=Standby, etc.).
Capacity Assist
Assist Time
Cooling Cut in
Cut out
E² Controller
Variables
Default
0 = Off
0
1 = On
0 to 999
0
0 to 23
0
1 to 8
0
1 to 8
0
1 to 8
0
0 to 6
0
300s
1.0°
F
0.0°
F
53