Download Print this page

Mitsubishi Electric PAC-SG85DR-E Installation Manual page 3

Filter dryer

Advertisement

【Fig2】
Filter dryer attachment diagram (horizontal attachment in unit)
Valve (liquid side)
②Connection pipe
 (liquid side)
ⅱ)When installing the filter dryer outside the unit, attach it to any position of extended pipe.
  Procure the connection pipe at local site.
【Fig3】
Filter dryer attachment diagram (attachment outside unit)
Outdoor unit
ⅲ)Heat insulation (to prevent dripping)
After attaching the filter dryer, wrap the heat insulator around the dryer.
 ※Tape the seam of heat insulator so that no gap is produced.
Also wrap heat insulator around other pipes.
The attachment of filter dryer is now complete.
3
Reattach the service panels, etc. to the original position.
4 Test Run
ⅰ)Perform test run according to the installation manual of unit, and be sure to execute gas leakage check and operation check.
E-244
Filter Dryer for Liquid Pipe of 12.7 PAC-SG85DR-E
①Filter dryer
③Heat insulator
Gas pipe
Liquid pipe
Enlarged view
①Filter dryer
③Heat insulator
Connection pipe (liquid side)