Technical Data - Window Master CompactSmoke WSC 104 Installation Instruction

Table of Contents

Advertisement

Technical data

5
Output current (nominal)
Secondary voltage
AUX
Motor lines
Smoke zones
Primary voltage
Power consumption
Leakage current
Inrush current on primary site
±24V change over time
Back-up batteries
Emergency power
Charging unit (integrated in WCA 1SS
card)
Priority
Cable monitoring
LED message OK, fault and alarm
Reopening the actuators
Connection cable
Operating conditions
Max actuator activation duration (duty
cycle)
Max allowed current drawn from the
battery when the primary power
source is disconnected
Max interruption time during switching
between power sources
Technical data
4A
Voltage
Open circuit voltage (no load)
Ripple at max load
24V DC, 500mA
1 motor line – the line can be either ±24V standard motor line or MotorLink
motor line. 1 smoke zone.
230V AC, 50Hz (85-264V AC, 47-63Hz)
2
1
min 0.3W
, typ. 0.2W
. At max load 110W
1) min. config. idle: 1 x break glass unit WSK 501 and 1 x smoke detector
WSA 311, system operational but no actuators are running
2) min idle:
1 x break glass unit WSK 501, 4 x break glass unit WSK 503, 4 x
smoke detector WSA 311 and 1 x rain sensor WLA 330
3) max load: 1 x break glass unit WSK 501, 4 x break glass unit WSK 503 and
10 x smoke detector WSA 311 in alarm
Max 1.4mA @ 240VAC
50A / 230VAC
Max. 7 x WSC 104 per 10A supply group.
Circuit breaker "C" characteristic.
min 500ms
2 x WSA 003 (12V / 3.4A),
Expected lifetime max 4 years, only use genuine WindowMaster batteries
>72 hours in accordance with EN 12101-10
Charging voltage: 27.7 – 27.8V at 20ºC
Charging current: 700mA current limited
Smoke signal has always highest priority
±24V standard actuators with end of line module and smoke detectors are
monitored.
®
Actuators with MotorLink
communication.
Back-up batteries are monitored by cyclic measuring
Green
all OK
Yellow
fault
Red
fire
Every 2.min. in 30min. after a SHE open (selectable) Pre-set: no reopening
Actuators
flexible max 6 mm² / solide max 10 mm²
Other
min 0,2mm² / max 1,5mm²
components
-5°C - +40°C, max. 95% relative humidity (not condensing)
EN 12101-10: Operation class A, Environmental class 1, IP30
ED 40% (4min. per 10min.)
4A incl. AUX
The total current consumption may not exceed 4A incl. load on AUX (max.
500mA)
<2.0sec
24V DC (±15%)
24V DC @ 20°C
150mVp-p
3
and break glass units are monitored by data
®
7