Performance data QHD750 up to QHD3600
-40 °F Variant
Specifications
Volume flow at dryer inlet refered to absolute
pressure of 1Bar, 20˚C, 0% RH
Volume flow at dryer inlet refered to absolute
pressure of 1Bar, 20˚C, 0% RH
Pressure drop over dryer
Pressure drop over dryer
Time of half a cycle
Purge time
Purge consumption
- During regeneration
- During regeneration
- average
- average
Maximum power consumption
Specifications
Volume flow at dryer inlet refered to absolute
pressure of 1Bar, 20˚C, 0% RH
Volume flow at dryer inlet refered to absolute
pressure of 1Bar, 20˚C, 0% RH
Pressure drop over dryer
Pressure drop over dryer
Time of half a cycle
Purge time
- During regeneration
- During regeneration
- average
- average
Maximum power consumption
9829 2151 14
Unit
QHD 750
QHD 900
cfm
750
901
l/s
425
425
psi
2.5
2.5
bar
0.17
0.17
s
258
258
s
175
175
%
25.2
25.2
SCFM
189
227
%
16.1
16.1
SCFM
128
154
Watt
20
20
Unit
QHD 1800 QHD 2300 QHD 2800 QHD 3600
cfm
1801
2331
l/s
850
1100
psi
2.5
2.5
bar
0.17
0.17
s
258
258
s
175
175
%
25.2
25.2
SCFM 454
587
%
16.1
16.1
SCFM 308
399
Watt
20
20
QHD 1100 QHD 1370
1123
1377
530
650
2.5
2.5
0.17
0.17
258
258
175
175
25.2
25.2
283
347
16.1
16.1
192
236
20
20
2818
3602
1330
1700
2.5
2.5
0.17
0.17
258
258
175
175
25.2
25.2
710
908
16.1
16.1
482
616
20
20
93