Troubleshooting

In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor
unit by checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Set every dip switch to OFF after checking.
7-Segment display and check code
Rotary switch setting
value
Indication
SW01
SW02
SW03
1
1
1
Outdoor unit check code
* If a check code has an sub code, the display indicates the check code for three seconds and the sub code for
one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Indication on 7-segment display on the outdoor unit
Sub code
E06
Number of indoor unit which received normally
E07
E08
Duplicated indoor addresses
E12
01 : Communication between indoor and outdoor
E15
00: Capacity over
E16
01 or more : No. of connected units
01: Other line outdoor connected
E20
02: Other line indoor connected
E31
IPDU quantity information
*1
80
F04
F06
F07
01: TL1 sensor
F08
F12
01: TS1 sensor
*
F13
1
F15
F16
F23
F24
F31
*
1
H01
1
*
H02
*
1
H03
H04
99-EN
7-segment
D600 D601 D602 D603 D604
LED
[ U. 1 .E r r ]
[ .
]
Display alternately every 2
seconds
Display contents
: Check code
: Sub code
Check code name
Decrease of number of indoor units
No indoor unit with a terminating resistor set
Indoor / Outdoor communication circuit trouble
Duplication of indoor addresses
Automatic address start trouble
No indoor unit during automatic address setting
Capacity over / Too many indoor units connected
Other line connected during automatic address setting
IPDU communication trouble
Communication trouble between MCU and sub MCU
TD sensor trouble
TE sensor trouble
TL1 sensor trouble
TO sensor trouble
TS1 sensor trouble
TH sensor (Board installed) trouble
Outdoor temp. sensor miswiring (TE, TL1)
Outdoor pressure sensor miswiring (Pd, Ps)
Ps sensor trouble
Pd sensor trouble
I/F EEPROM trouble
Compressor breakdown
Compressor trouble (Lock)
Current detective circuit system trouble
Compressor trouble (Overheat)
H06
*
1
H17
J30
Detected indoor addresses
L02
Detected indoor addresses
L04
L06
Number of indoor units with priority
L08
L10
L11
Detected indoor address
L13
Detected indoor address
L14
Detected indoor address
IPDU quantity information *
L29
1
L30
Detected indoor address
P03
1
*
P04
P05
00
*
1
*
*
E (
: Fan motor number)
P07
P10
Detected indoor address
P11
P13
P14
01 : Outdoor unit service valve is close
01 : TS1 condition
P15
02 : TD condition
P19
P20
*
0 : Elemental device short
*
1 : Position detective circuit trouble
*
3 : Fan motor lock trouble
P22
*
4 : Motor current trouble
*
5 : Synchronize, step out trouble
*
(
: Fan motor number)
*
P26
1
*
1
P29
*1 IPDU number information
01 : Compressor
08 : Fan
09 : Compressor and Fan
– 50 –
Low-pressure protective operation
Compressor trouble (Out of sync)
Refrigerant leak detection
Model mismatch of indoor and outdoor unit
Outdoor system address duplicated
Duplication of indoor units with priority
Indoor unit address / Group address unset
Outdoor unit capacity unset
Unsuitable safety device connected
Mismatch of safety device settings
Safety device nonconformity
IPDU quantity trouble
External interlock of indoor unit
Discharge temp TD trouble
High-pressure switch trouble
Power detection trouble
Compressor Vdc trouble
Fan motor Vdc trouble
Heat sink overheat trouble
Indoor overflow trouble
Outdoor unit heat exchanger freezing trouble
Outdoor unit liquid back detection trouble
Other refrigerant cycle protection
Gas leak detection
4-way valve operation trouble
High-pressure protective operation
Outdoor unit fan trouble
Compressor IPM short protection trouble
Compressor position detective circuit trouble
EN
100-EN