CAUTION
1. Install the outdoor unit in a location where the discharge air is not blocked.
2. When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high
stories of a building, secure normal fan operation by using a duct or wind shield.
3. When installing the outdoor unit in a location that is constantly exposed to strong winds such as on the upper
stairs or rooftop of a building, apply the wind-proofing measures referred to in the following examples.
1) Install the unit so that its discharge port faces the wall of the building.
Keep a distance 500 mm or more between the unit and wall surface.
2) Consider the wind direction during the operational season of the air conditioner, and install the unit so that
the discharge port is set at a right angle relative to the wind direction.
Strong wind
4. When installing the unit in an area where snowfalls may be heavy, take steps to prevent the unit from being
adversely affected by the fallen or accumulated snow.
• Either make the foundation higher or install a stand (which is high enough to ensure that the unit will be
above the fallen or accumulated snow) and place the unit on it.
• Attach a snow shield (locally procured).
<Example>
Snow shield
47-EN
500 mm
Strong wind
Snow shield
 Necessary space for installation
Be sure to observe the necessary space for installation
Installation the outdoor unit in a well-ventilated location.
Failure to do so may cause short-circuit (intake of discharge air) or performance deterioration due to locations
around the outdoor unit.
Single unit installation
When there is an obstacle on
When there is an obstacle
the back side
on the front side
(Front, sides, and top are free)
(Back, sides, and top are free)
150 or
more
When there are obstacles on the top
When there are obstacles on
and front sides
the back and top sides
(Back and sides are free)
(Front and sides are free)
1000 or
more
1000 or more
– 24 –
When there are obstacles on the front
and back sides
(Sides and top are free)
150 or
500 or more
1000 or
more
more
When there are obstacles on the
back and sides
(Front and top are free)
* The height of the obstacle should be
lower than that of the outdoor unit.
500 or
more
500 or
more
200 or
300 or
more
more