13. Flush Shutter Calibration

Automatic calibration
Automatic calibration is a process during which the Flush Shutter learns the position of the limit
switches.
Shutter positioning calibration
(par. 71 set to 0)
There are two options to calibrate the device:
• Calibration through the main gateway (hub) UI
1) Include the device into the Z-Wave network according to the instructions for inclusion.
2) Set the parameter 78 (Forced Flush Shutter calibration) value to 1.
3) Flush Shutter performs the calibration process, completing full cycle - up, down and up
again.
4) Set the parameter 78 (Forced Flush Shutter calibration) value to 0.
• Calibration through the inputs I1 and I2
1) Include the device into the wireless network according to the instructions for inclusion.
2) Quick press the switch/push-button connected to I1 input and wait until the Shutter
reaches the upper limit switch.
3) Quick press the switch/push-button connected to I2 input and wait until the Shutter
reaches the lower limit switch.
4) Quick press the switch/push-button connected to I1 input and wait until the Shutter
reaches the upper limit switch.
Slates tilting position calibration
(par. 71 set to 1)
When enabling venetian blinds mode, position calibration for slats titling must be done. After
doing this, the position and angle of the slates can be set. By default, full turn time for slates is
set to 1.5s. This value can be changed with parameter 72.
40
EN.