Bosch WORCESTER Greenstar Heatslave II 12/18 Installation, Commissioning And Servicing Instruction Manual page 42

Floor standing oil-fired condensing combination boiler using conventional and room sealed flue
Table of Contents

Advertisement

Commissioning
1
2
3
Fig. 69 Start up screens
Screen display
All possible screen symbols are displayed briefly during start up.
Extended diagnostic features have rendered the greyed out symbols not
required for the operation of this appliance.
42
1
2
3
Fig. 70
[1]
Central heating symbol
Displays this symbol during CH demand.
[2]
Hot water symbol
Displays this symbol during DHW demand (DHW flow rate >
2 litres per minute) and tank reheat.
[3]
Weather Compensation active symbol
Displays this symbol only if a Weather Compensation sensor has
been fitted to the appliance and is active.
[4]
Alert symbol
Displays with the boiler status code and diagnostic code during a
fault condition.
[5]
Service mode symbol
Displays when in the service menu.
[6]
Centigrade symbol
Displays next to the temperature reading.
[7]
Confirmation symbol
This symbol confirms a manual change.
[8]
Alpha/Numerical display
Displays a temperature or boiler status code.
[9]
Text display
Displays ECO or diagnostic code.
Status code
During normal operation various status codes can be displayed by
pressing the service button.
The first screen of the information menu displays the current status
code, this will change as the boiler runs through the various modes and
sequences.
These are not faults, but provide information concerning the current
status.
Status
Code
200
CH active
The Central Heating system is being heated.
201
DHW active
The Domestic Hot Water is being heated/
tank is being heated.
202
CH Anti rapid-
Time delay to prevent rapid-cycling of the
cycle mode
boiler on the room thermostat.
203
System stand-by The boiler has no CH or DHW demands.
270
Power up mode The boiler is ON, warming up and running self
check routines. This lasts approximately
35 seconds.
358
Three way valve
Anti-seize operation. If the diverter valve has
anti-seize
not moved in 24 hours, the valve is operated
to prevent seizing, duration approximately
10 seconds.
Table 8
Greenstar Heatslave II
4
5
6 7
6 720 805 209-39.1TL
9
8
2022 +