4 – Cabinet Installation
4
(Optional) If you wish to provide an additional measure of stability, you can attach the 2
shipping brackets, using the hardware that attached the Distribution Center to the shipping
pallet. Use a 13 mm open-end wrench to connect the brackets to the outer
bracket mounting points of the Distribution Center. Attach the brackets to secure mounting
points in the floor using user-supplied hardware or Tripp Lite's Bolt-Down Kit (Part #
SRBOLTDOWN).

4.5 Ground Connection

All the parts of the Distribution Center are grounded to the frame of the enclosure. Use the
Distribution Center's front or rear threaded grounding point
connect the frame of the Distribution Center directly to your facility's earth ground connection
with an 8 AWG wire. Route the ground wire under the Distribution Center's frame to ensure
unhindered door operation. WARNING: Attach the Distribution Center to earth ground
separately—not daisy-chained with other equipment. Do not use the Distribution Center
without an earth ground connection.
5 – Wiring Installation
5.1 Preparation
Warning: All wiring must be performed by a qualified, certified electrician.
Review the entire manual before wiring the Distribution Center, including all warnings.
Consider how you will route power into the unit, wire all internal connections and route power out of the unit, making careful measurements.
Input wiring measurements will differ for concrete floor and raised floor installations. See Section 5.5 for more information.
The cabling to wire the 3-phase power source to the Distribution Center is not included with the Distribution Center. Make sure the electrician
supplies the appropriate cabling, in accordance with NEC and all other applicable local or national electrical regulations.
Routing output cord sets from the top of the Distribution Center to your racks and PDUs should be managed systematically, with proper data and
power cable segregation. Tripp Lite offers a full line of external cable management accessories (sold separately), including SRCABLELADDER,
SRCABLETRAY and SRCABLETRAYEXP.
Ordering Required Breakers and Cord Sets
Decide how many and what type of output breakers and cord sets you need (see below).
Contact your distributor or go to www.tripplite.com to order.
Warning: Use Tripp Lite breakers and cord sets only.
Note: When ordering cord sets, order longer cords than the minimum required. The electrician can trim the ROJ section for a custom fit.
Available Output Branch Circuit Breakers
Tripp Lite #
SUBB120
SUBB230
SUBB320
SUBB330
continued
and an M6 screw (included) to
A
Description
Single-Pole, 20A Breaker
2-Pole, 30A Breaker
3-Pole, 20A Breaker
3-Pole, 30A Breaker
or inner
A
B
4
7
B
A
A
EARTH
GROUND