Safety output-extension module

Advertisement

Safety Output-Extension Module TE- OR3
User Information
Maintenance
The device must be checked once per month for proper
function and for signs of tampering and bypassing of the
safety function.
The device is otherwise maintenance free, provided that it
was installed properly.
Device does not switch on:
What to do in
Check the wiring by comparing it to the wiring diagrams.
Case of a Fault?
Check the jumper between In and Ox.
Check the correct fit on the DIN rail.
If the feedback loop is used, is it closed?
Safety
Load (DC-13; 24 V) per contact
Characteristics
Max. lifetime [years]
according to
EN ISO 13849-1
Category
PL
PFHd [1/h]
nop [Cycles per year]
Safety
Calculation under the following conditions:
Characteristics
Days of operation per year: 365; Hours of operation per day: 24; Switching-cycle per hour: 1;
according to
Maximum load AC-15 / DC-13
EN 62061 /
Max. lifetime [years]
EN 61508
Proof test interval [years]
PFH [1/h]
PFD
SILCL
Advice: For other applications than described, please contact the manufacturer for further information.
Technical data
In compliance with
Operating voltage
Allowable tolerance
Number of modules per safety output of the basic module
Safety contact
Auxiliary contacts
Switching voltage max.
Contact rating of safety contacts (13-14, 23-24, 33-34)
(6 switching cycles/ min)
Cumulative current
Contact rating of auxiliary contact (41-42)
Minimum voltage/ current
External fuses for safety contacts
Wire width
Contact material
Service life
Rated impulse withstand voltage
Dielectric strength (EN 60664-1)
Rated insulation voltage
Protection
Temperature range
Degree of pollution
Overvoltage category
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • info@zander-aachen.de • www.zander-aachen.de
AVG
For furnaces which operate continuously where regular
inspection at sufficient short intervals in accordance to EN
50156-1 may not be performed, are excluded from this (only
TE-OR3D).
If the fault still exists, perform the steps listed under
"Commissioning Procedure".
If these steps do not remedy the fault either, return the
device to the manufacturer for examination.
Opening the device is impermissible and will void the
warranty.
<= 0,1 A
<= 1 A
20
20
4
4
e
e
1,2E-08
1,2E-08
<= 500.000
<= 350.000
20
20
3,31E-10
2,87E-05
3
EN 60204-1; DIN EN ISO 13849-1; EN 62061;
IEC 61508 Parts 1-2 and 4-7; IEC 61511-1;
EN 50156-1; EN 746-2 (only TE-OR3D)
DC 24 V
+ / - 10 %
Max. 5 modules
3 NO
1 NC
AC 250 V
AC:
250 V, 2000 VA, 8 A for resistive load
250 V, 5 A for AC-15
DC:
30 V, 240 W, 8 A for resistive load
24 V, 4 A for DC-13
Max. 15 A (13-14, 23-24, 33-34)
AC: 250 V, 500 VA, 2 A for resistive load
DC: 30 V, 60 W, 2 A for resistive load
24 V, 10 mA
10 A gG
6 A gG for applications acc. to EN 50156-1
0.14 - 2.5 mm
AgSnO
2
mech. approx. 1 x 10
2.5 kV (control voltage / contacts)
6 kV between safety relays contacts,
control lines and internal logic
250 V
IP20
-15 °C up to +55 °C
2
(EN 60664-1)
3
(EN 60664-1)
<= 2 A
20
4
e
1,2E-08
<= 100.000
(See Chapter 10.5.5.3.4)
2
7
cycles
H10
Ver. A
E61-058-00
3