Safety Output-Extension Module TE- OR3
User Information
Applications
The device has to be wired as shown in Fig. 1.
Wiring diagram
Fig. 1:
Single channel emergency stop. (category 4, up to PL e / SIL 3)
Connecting load to safety contacts.
(Figure shows example. Voltage „+V" according to technical data)
If a feedback loop is necessary for the application, it can be wired to
the auxiliary contact 41-42 (e.g. like in Fig.1).
Commissioning
Advice: Follow the guidelines in „Electrical Connection" during the start-up.
Procedure
1. Feedback loop:
If a feedback loop is necessary for the application, it has to
be wired as shown in Fig.1
2. Connecting control line:
Connect the terminal In and the terminal O1, O2 or O3 with
a jumper, depending on which output of the basic module
the TE-OR3 shall react.
Caution: Wiring only in de-energized state.
3. Starting the device:
Turning on the safety output of the basic module.
Caution:
The safety contacts will close immediately by turning on the
control line.
The LEDs K1 and K2 are lit.
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany
Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138 • info@zander-aachen.de • www.zander-aachen.de
Each expansion module may only be connected
to one safety output of the basic device.
Multiple connection is not permitted.
Caution:
Safety contacts will be activated immediately by switching on the
control line.
Up to 5 extension modules may be connected to each safety output of
the basic module.
4. Triggering safety function:
Turning off the safety output of the basic module. The
safety contacts will open immediately.
The LEDs K1 and K2 go out.
5. Reactivation:
Turning on the safety output of the basic module. The
safety contacts will close immediately.
The LEDs K1 and K2 are lit.