Cool/freeze thermostat with a temperature sensor, two defrost sensors, a day/night digital input, relays for defrost-1, defrost-2, fan, cool and alarm (8 pages)
Page 1
Range: -10,0/+40,0 °C per 0,1°C * Installation. On the Topside of the ALFA 31 DP you can see how the sensor, power supply and relay have to be connected. After connecting the ALFA 31 DP to the power supply, a self test function is started. As this test is finished the measured temperature appears in the display.
Page 2
20 seconds no key is pushed, the ALFA 31 DP changes to its normal operation mode. * Adjustment sensor. The sensor can be adjusted by using the Sensor Offset (parameter 04). Indicates the ALFA 31 DP e.g. 2°C too much, the Sensor Offset has to de decreased by 2°C.
Page 3
* Parameter ALFA 31 DP. PARA- DESCRIPTION PARAMETER RANGE DEFAULT METER VALUE Switching differential 0,1..10°C Minimum setpoint -10..+40°C -10.0 Maximum setpoint -10..+40°C +40.0 Offset temperature sensor -10..+10°C Startup delay after power 0..99 Min. failure Relay on at sensor failure 0 = No...
Page 4
* Dimensions * Connections * Function diagram...