About This Product; Precautions For Using The R410A Refrigerant - Fujitsu AIRSTAGE K00250LW Addendum

Outdoor unit
Table of Contents

Advertisement

WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts.
Using non-specifi ed parts will cause serious accidents such as falling unit, refriger-
ant leakage, water leakage, electric shock, and fi re.
To install a unit that uses the R410A refrigerant, use dedicated tools and piping
materials that have been manufactured specifi cally for R410A use.
Because the pressure of the R410A refrigerant is approximately 1.6 times higher
than the R22, failure to use dedicated piping material or improper installation can
cause rupture or injury.
It will also cause serious accidents such as refrigerant leakage, water leakage,
electric shock, and fi re.
Do not introduce any substance other than the prescribed refrigerant into the refrig-
eration cycle.
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will be-
come abnormally high and cause the piping to rupture.
Be sure to install the unit as prescribed, so that it can withstand earthquakes and
typhoons or other strong winds.
Improper installation can cause the unit to topple or fall, or other accidents.
Ensure that the outdoor unit is securely installed at a place that can withstand the
weight of the unit.
Improper installation will cause injuries caused by falling unit.
If there is a refrigerant leakage, make sure that it does not exceed the concentration
limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents
such as oxygen starvation.
If a refrigerant leakage occurs during operation, immediately vacate the premises
and thoroughly ventilate the area.
If the refrigerant is exposed to fi re, it will create a hazardous gas.
Electrical work must be performed in accordance with this Installation manual by a
person certifi ed under the national or regional regulations. Be sure to use a dedi-
cated circuit for the unit.
An insuffi cient power supply circuit or improperly performed electrical work can
cause serious accidents such as electric shock or fi re.
For wiring, use the prescribed type of cables, connect them securely, making sure
that there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as
overheating the terminals, electric shock, or fi re.
Do not turn ON the power until all work has been completed.
Turning ON the power before the work is completed can cause serious accidents
such as electric shock or fi re.
After the installation, make sure there is no refrigerant leakage.
If the refrigerant leaks into the room and becomes exposed to a source of fi re such
as a fan heater, stove, or burner, it will create a hazardous gas.
Use a wall hole pipe. Otherwise, it may cause a short circuit.
Do not place the outdoor unit near the handrail of the balcony.
Children may climb onto the outdoor unit, lean over the handrail and fall over.
Use only a specifi ed power cable. Poor connection, poor insulation, and exceeding the
allowable current will lead to electric shock and fi re.
Attach the connecting cables securely to the terminal. Or secure it fi rmly with a "wir-
ing suppressor".
Loose connection will lead to malfunction, electric shock, and fi re.
Install a breaker to cut off all AC main current at the same time.
If you do not install a breaker, it may cause electric shock and fi re.
During installation, make sure that the refrigerant pipe is attached fi rmly before you
run the compressor.
Do not operate the compressor under the condition of refrigerant piping not at-
tached properly with 2-way or 3-way valve open. This may cause abnormal pres-
sure in the refrigeration cycle that leads to rupture and even injury.
During the pump-down operation, make sure that the compressor is turned off
before you remove the refrigerant piping. Do not remove the connection pipe while
the compressor is in operation with 2-way or 3-way valve open. This may cause
abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
If there is a possibility of touching the fan during maintenance, make sure to turn
OFF the power before implementing the maintenance. Even if operations are
suspended, the fan of outdoor unit sometimes rotates, so if the fan rotates suddenly
while in contact with you may cause serious injury.
CAUTION
This unit must be installed by qualifi ed personnel with a capacity certifi cate for
handling refrigerant fl uids. Refer to regulation and laws in use on installation place.
The installation must be carried out in compliance with regulations in force in the
place of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone
or with non-authorized by the manufacturer.
This unit contains no user-serviceable parts. Always consult authorized service
personnel to repairs.
When moving, consult authorized service personnel for disconnection and installa-
tion of the unit.
• Obtain the distribution network operator's agreement about the power capacity
of the power supply system, specifi cation of the cable and the harmonic current,
and etc. when you connect the outdoor unit with the power supply.
• This unit must be connected to a power supply with impedance of 0.33 ohm and
below. If the power supply does not satisfy this requirement, please consult the
power supplier.
• This product is intended for professional use.
Be sure to use a dedicated power circuit.
Never use a power supply shared by another appliance.
Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fall or the unit to leak water.
• Area fi lled with mineral oil or containing a large amount of splashed oil or
steam, such as a kitchen.
It will deteriorate plastic parts, causing the parts to fall or the unit to leak
water.
• Area that generates substances that adversely affect the equipment, such as
sulfuric gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
• Area containing equipment that generates electromagnetic interference.
It will cause the control system to malfunction, preventing the unit from oper-
ating normally.
• Area that can cause combustible gas to leak, contains suspended carbon
fi bers or fl ammable dust, or volatile infl ammables such as paint thinner or
gasoline.
If gas leaks and settles around the unit, it can cause a fi re.
• Avoid installing the unit at places where it will come into contact with animals'
urine or ammonia.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
Do not use the unit for special purposes, such as storing food, raising animals,
growing plants, or preserving precision devices or art objects. It can degrade the
quality of the preserved or stored objects.
Ground the unit. Do not connect the ground wire to a gas pipe, water pipe, lightning
rod, or a telephone ground wire. Improper grounding may cause electric shock.
Perform draining for the unit according to the Installation manual. Check that the
water is properly drained.
If the drain processing is improperly installed, water may drip down from the unit,
wetting the furniture.
Do not touch the fi ns with bare hands.
Be sure not to start or stop the operation of air conditioning with power breaker.
Otherwise, it may cause malfunction or water leakage.
When setting it up near the equipment that generates electromagnetic waves and
the equipment that generates the higher harmonics wave, be sure to take measures
against noise. Otherwise, it may cause malfunction or failure.
When energizing to the crankcase heater, please turn on the power 12 hours or
earlier before operation begins. When the energizing time is short, it may cause
failure. Besides, please do not turn off power during the busy season.
Children should be monitored to ensure they do not play with the device.
This product is not intended to be used by people (including children) with physical,
sensory or mental disability, or persons lacking experience or knowledge unless
they have been given by the through a person responsible for their safety, supervi-
sion or instruction concerning the use of the device.

2. ABOUT THIS PRODUCT

2. 1.

Precautions for using the R410A refrigerant

Pay careful attention to the following points :
Since the working pressure is 1.6 times higher than that of R22 models, some of the
piping and installation and service tools are special. (See the table in the SPECIAL
TOOLS FOR R410A section.)
Especially, when replacing a conventional refrigerant (other than R410A) model with
a new refrigerant R410A model, always replace the conventional piping and fl are
nuts with the R410A piping and fl are nuts.
Models that use refrigerant R410A have a different charging port thread diameter
to prevent erroneous charging with R22, R407C and for safety. Therefore, check
beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads
per inch.]
Be more careful than the installation of the refrigerant (other than R410A) models,
not to enter foreign matters (oil, water, etc.) and other refrigerant into the piping.
Also, when storing the piping, securely seal the openings by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composi-
tion of the gas and liquid phases, and always charge from the liquid phase side
whose composition is stable.
En-2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents