Boiler
(cont.)
Coding in the delivered condition
28:0
No burner interval igni-
tion
2E:0
Without external exten-
sion
30:0
Never adjust
31:...
Set speed of the internal
circulation pump when
operated as boiler circuit
pump %, specified by the
boiler coding card
38:0
Status burner control unit:
Operational (no fault)
DHW
Coding
Coding in the delivered condition
DHW
56:0
Set DHW temperature
adjustable from 10 to
60 °C
58:0
Without auxiliary function
for DHW heating
Possible change
28:1
Time interval adjustable
to
from 1 to 24 h. The burner
28:24
is force-started once every
30 s (only when operating
with LPG).
2E:1
With external extension
(automatic recognition)
31:0
Set speed adjustable from
to
0 to 100 %
31:100
Status burner control unit:
38:≠0
Fault
Possible change
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject to
boiler coding card.
Observe the max. permis-
sible DHW temperature.
58:10
Input of a second set DHW
to
temperature, adjustable
58:60
from 10 to 60 °C (observe
coding addresses "56" and
"63")
Code 2
75