Din rail 12v 4a intelligent power supply (33 pages)
Summary of Contents for Genetec SY-SIX-PSU-DIN-8A
Page 1
DIN Rail 12V 8A Intelligent Power Supply SY-SIX-PSU-DIN-8A Installation Manual Document last updated June 12, 2019...
Page 2
In no event shall Genetec Inc. be liable to any person or entity with respect to any loss or damage that is incidental to or consequential upon the instructions found in this document or the computer software and hardware products described herein.
Contents Introduction Installation Requirements Grounding Requirements Safety Grounding Earth Ground Connection Mounting Removal Cabinet Tamper Switch Wiring Diagram Mains Power Backup Battery Encrypted Module Network Module Wiring End of Line (EOL) Resistors Output Load Connection Output Current Influence on Output Load Operation Core Temperature on Output Load Operation Inputs Trouble Inputs...
Page 4
Error Code Indication Error Code Display Mechanical Diagram Mechanical Layout Technical Specifications New Zealand and Australia European Standards FCC Compliance Statements Industry Canada Statement Last updated June 2019...
Introduction The DIN Rail 12V 8A Intelligent Power Supply provides 12VDC power suited to powering security, access control or automation devices along with large numbers of Synergis network powered modules, and allows for simple and powerful monitoring of supply currents and voltages. Flexible module network architecture allows large numbers of modules to be connected to the RS-485 module network.
Installation Requirements This equipment is to be installed in accordance with: The product installation instructions The National Electrical Code, ANSI/NFPA 70 The Canadian Electrical Code, Part I, CSA C22.1 The Local Authority Having Jurisdiction (AHJ) Installation Requirements Last updated June 2019...
Grounding Requirements An effectively grounded product is one that is intentionally connected to earth ground through a ground connection or connections of sufficiently low impedance and having sufficient current-carrying capacity to prevent elevated voltages which may result in undue hazard to connected equipment or to persons. Grounding of the Synergis system is done for three basic reasons: 1.
Page 8
Note that the DIN Rail enclosure earth terminal is connected to the power supply V- terminal. There must be only one single earth grounding point per system. Grounding Requirements Last updated June 2019...
Mounting The Power Supply is designed to be mounted on standard DIN Rail either in dedicated DIN cabinets or generic DIN Rail mounting strip. It can also be hung from the top mount screw slot and permanently fastened using the hole in the attachment clip When installing the Power Supply ensure that there is adequate clearance around all sides of the device and that air flow to the vents of the unit is not restricted.
Mains Power The Power Supply should be supplied by a dedicated electrical power source rated for a minimum 5 Amp load and have a dedicated circuit breaker. Connect the Power Supply module to mains input via an appropriate IEC-C7 90 degree cable. The earth wire shall be routed to the V- terminal on the Power Supply.
Backup Battery It is recommended that a minimum of a 7Ah battery is used as the main backup battery. From the accessory bag provided, connect the RED and BLACK battery termination wires to the B+ and B- plugs. Connect the spade terminals to the battery as shown below. Connection of the battery in reverse will not damage the Power Supply but will cause the battery circuit to disconnect until correct connection is made.
Encrypted Module Network The Power Supply incorporates encrypted RS-485 communications technology. Network power is supplied by the N+ and N- terminals. Connection of the communications and network power should be performed according to the diagram shown. It is important that the N+ network communications power be 12VDC supplied from an independent battery backed power supply unit or a networked module capable of supplying the required voltage to all devices on the RS-485 network.
Module Wiring The recommended module network wiring specifications are: Belden 9842 or equivalent 24AWG twisted pair with characteristic impedance of 120ohm Maximum total length of cable is 900m (3000ft) CAT5e / CAT6 are also supported for data transmission when using ground in the same cable (to a maximum length 100m (328ft)) Warning: Unused wires in the cable must not be used to carry power to other devices.
Output Load Connection The Power Supply provides two sets of 12VDC output terminals, V1+ and V2+. Both V1+ and V2+ outputs are individually fused, with 6 terminals associated to each output and its individual fuse. A maximum current output of 6.0 Amps at 12VDC can be provided across each output at any one time. However, if a single current output of 8.0 Amps is required, then both outputs need to be connected together in parallel.
Output Current Influence on Output Load Operation The table below helps illustrate how the total output current drawn from the power supply module influences the operation of V1 and V2 outputs. Output Load Current 8.0 - 8.2A - Short Output Load Operation Status 0 - 8.0A 8.2A Circuit...
Inputs The Power Supply has no physical input connections. The Power Supply monitors 8 trouble inputs used to report trouble conditions. A trouble input is in most cases not physically connected with an input in to the Power Supply; rather it is related to a status condition within the system. For example a module communication fault causes a trouble input to open as a result of the communication failure.
Outputs The Power Supply has two 50mA outputs that can operate as either programmable outputs (PGMs) or as predefined status outputs, depending on the network status of the module on the Synergis system. Online Mode Upon successfully completing the initial registration with any Synergis System Controller, the outputs of Power Supply operate in Online Mode.
AC Fail Status Output The AC Fail Status Output has a Solid State relay. The output relay contacts disconnect (Normally Open) when AC power is removed and the unit remains running on backup battery power. Upon restoring AC power, the output relay will revert back to its default state (Normally Closed). This output is suited for connection to an input on a Synergis module with spare inputs available so that the Power Supply AC status can be externally monitored.
Intelligent Monitoring The Power Supply is able to relay information about critical system voltages, currents and temperature to the Synergis Controller by registering as an Analog Expander module on the Synergis network. The Synergis Controller can then store these values in system registers that can be viewed live from the Synergis interface.
Address Configuration The address of the Power Supply is configured via programming and will require entry of the module serial number. The serial number can be found on the identification sticker on the product. Refer to the Synergis System Controller installation manual for address programming details. Address Configuration Last updated June 2019...
LED Indicators The Power Supply includes comprehensive diagnostic indicators that can aid in diagnosing faults and conditions. In some cases an indicator may have multiple meanings depending on the status indicator display at the time. Status Indicator The status indicator displays the module status. State Description Fast Flash (green)
V1 Output/V2 Output Indicators The V1 and V2 output indicators show the status of the 12VDC output. State Description On (green) 12VD output operating OK Flashing (red) 12VDC output failure Battery Indicator The Battery indicator shows the status of the backup battery. State Description Flashing (red)
Error Code Indication When the module attempts to register or communicate with the system controller a registration error can be generated indicating that it was not successful. Error Code Display The following table is only valid if the FAULT indicator is CONSTANTLY ON and the STATUS indicator is FLASHING RED.
Mechanical Diagram The mechanical diagram shown below outlines the essential details needed to help ensure the correct installation of the Power Supply. Mechanical Diagram Last updated June 2019...
Mechanical Layout The mechanical layout shown below outlines the essential details needed to help ensure the correct installation of the Power Supply. Mechanical Layout Last updated June 2019...
Genetec Inc. continually strives to increase the performance of its products. As a result these specifications may change without notice. We recommend consulting our website (www.genetec.com) for the latest documentation and product information.
New Zealand and Australia General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards. New Zealand and Australia Last updated June 2019...
European Standards CE Statement Conforms to European Union (EU) Low Voltage Directive (LVD) 2014/35/EC, Electro-Magnetic Compatibility (EMC) Directive 2014/30/EU and RoHS Recast (RoHS2) Directive: 2011/65/EU.Directive: 2011/65/EU EU + Amendment Directive (EU) 2015/863. The CE mark indicates that this product complies with the European requirements for safety, health, environmental and customer protection.
Page 30
Radiated disturbance EN 55032:2015 Enclosure EN-DIN-24 for all Synergis products has been tested and certified to EN50131. By design, all Synergis DIN Rail Enclosures comply with the EN50131 standards. Tamper protection against removal of the cover as well as removal from mounting is provided by tamper switch. Warning: Enclosures supplied by 3rd parties may not be EN50131-compliant, and should not be claimed as such.
FCC Compliance Statements FCC PART 15, WARNINGS: INFORMATION TO USER This equipment complies with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Industry Canada Statement This class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. CAN ICES-3 (A)/NMB-3(A) Industry Canada Statement Last updated June 2019...
Need help?
Do you have a question about the SY-SIX-PSU-DIN-8A and is the answer not in the manual?
Questions and answers