Eltek Valere PSC312-220/24-50 User Manual

Dc/dc converter

Advertisement

Quick Links

DC/DC Converter
PSC312-220/24-50
Art.-No. 201-012-748.220
USER MANUAL
UM_PSC312_220_24_21TE_E_R1.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSC312-220/24-50 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eltek Valere PSC312-220/24-50

  • Page 1 DC/DC Converter PSC312-220/24-50 Art.-No. 201-012-748.220 USER MANUAL UM_PSC312_220_24_21TE_E_R1.0...
  • Page 2 Supplier: ELTEK VALERE INDUSTRIAL GmbH Schillerstraße 16 D-32052 Herford + 49 (0) 5221 1708-210 + 49 (0) 5221 1708-222 Email Info.industrial@eltekvalere.com Internet http://www.eltekvalere-industrial.com © Copyright ELTEK VALERE INDUSTRIAL 2009. All rights reserved. ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 3 DC/DC converter PSC312-220/24-50 User Manual Page 3 (16) The current revision status of this user manual: Revision: Date: 2009-02-24 Revision Description of change Writer Date First edition on the basis of the German manual 2009-02-24 “UM_PSC312_220_24_21TE_G_R1.0” ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 4: Table Of Contents

    7.1 Dimensional Drawings ............................15 Index of figures Figure 1) Sub rack fully equipped with four converters PSC ...................7 Figure 2) Front view................................7 Figure 3) Male connectors ..............................8 Figure 5) Air flow ..................................9 Figure 7) Module dimensions ............................15 ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 5: Safety Instructions And Waste Disposal Rules

    The above statement from EU directive 2002/96/EC applies to all electric modules installed within EU countries. In countries outside the EU, different rules may apply regarding waste disposal of electric modules. For more information about waste disposal of your discarded equipment, contact your ELTEK VALERE INDUSTRIAL partner. ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 6: General Information

    3. Type Range/Equipment Type Designation Material Code Nominal Output Voltage Nominal Output Current PSC312-220/24-50 201-012-748.220 3.1 Main Data Nominal input voltage: 220V Nominal input current: 6.2A Nominal output power: 1200W For more specific data, see Section ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 7: Available Options And Assembly Equipment

    • Vout> • ALARM For more information about the LED indicators, section 4.4 Two captive screws are used for each module to secure it to the sub rack (components of the module) Figure 2) Front view ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 8: Rear Side Connection

    AGND - - - Hardwarecoding CODE2 Hardwarecoding CODE1 Collective Alarm NC Collective Alarm COM Collective Alarm NO - - - - - - (+) output voltage sense link (-) Output (-) Output (+) Output (+) Output ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 9: Cooling And Air Flow Direction

    Several modules in a system or parallel connection can be monitored through the CAN-Bus by a central UPC3 DC controller unit. The following parameters of a specific rectifier unit can be monitored: • Output voltage • Output current • Device temperature • Device status ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 10: Handling

    Note: Before removal of a module it must be switched off by the external input fuse! CAUTION! After switching off the module the internal capacitors are still fully charged. Do not touch connector pins as they can still be charged with dangerous voltage after disconnection. ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 11: Charge Characteristic Curve

    *For factory setting of the output voltage threshold values, see section 4.6 **The module is equipped with an isolated signalling contact (normally open contact). The maximum load is 60V /500mA. The contact is time-delayed and reacts after approx. 10 sec. ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 12: Monitoring

    *For factory settings of the output voltage threshold values, see section 4.6 4.6 Threshold/Default Value Adjustment The following threshold/default values (factory settings) are stored in the PSC312: Default 24V version Vo (V 24.0 V> (V 30.0 V< (V 20.1 Iconst (A 50.0 ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 13: Maintenance

    If an external sensor lead is used for the output Check voltage, is the connection faultless? If the module still does not work even though all checks have been done, contact your sales agent or the ELTEK VALERE INDUSTRIAL service department. ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 14: Technical Specifications

    Internal output fuse Standard Features: LED signalling Input OK (green), Vo OK (green), Vo> (red), Alarm (red) Main processor 16Bit Fujitsu Isolated signalling contact Collective alarm; maximum load: 60V /500mA Communications interface CAN-Bus, proprietary protocol ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 15: Dimensional Drawings

    Colour (front panel) RAL 7035; black imprint Compliances: CE conformity Compliance to safety EN60950-1; VDE0100 T410; VDE0110; EN50178; EN60146 standards Compliance to EMC standards EN55022/24 (ITE), class “A“; EN61000-4 T2-5 7.1 Dimensional Drawings Figure 7) Module dimensions ELTEK VALERE ©2009 UM_PSC312_220_24_21TE_E_R1.0...
  • Page 16 Supplier: ELTEK VALERE INDUSTRIAL GmbH Schillerstraße 16 D-32052 Herford + 49 (0) 5221 1708-210 + 49 (0) 5221 1708-222 Email Info.industrial@eltekvalere.com Internet http://www.eltekvalere-industrial.com © Copyright ELTEK VALERE INDUSTRIAL 2009. All rights reserved.

This manual is also suitable for:

201-012-748.220

Table of Contents