  • Page 1 DC/DC CONVERTER PSC305-LV USER MANUAL UM_PSC305LV_E_R2.0...
  • Page 2 89/339 EWG (electromagnetic compatibility) if the installation and operation instructions are followed. Supplier: ELTEK VALERE INDUSTRIAL GmbH Schillerstraße 16 D-32052 Herford + 49 (0) 5221 1708-210 + 49 (0) 5221 1708-222 Email Info.industrial@eltekvalere.com Internet http://www.eltekvalere-industrial.com © Copyright ELTEK VALERE INDUSTRIAL 2007. All rights reserved. ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 3 First edition 2007-11-06 Section “Commissioning” reworked, minor text 2008-02-15 modifications Minor layout & text modifications, new revision status numbering (X.X) introduced, index of figures 2009-01-05 inserted. Default values in section 4.6 changed, minor text 2009-03-24 modifications. ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 4: Table Of Contents

    Figure 1.) DC/DC power rack fully equipped ........................7 Figure 2.) Fan rack ................................7 Figure 3.) Front view................................8 Figure 4.) Rear side connector............................9 Figure 5.) Module airflow..............................10 Figure 6.) Output power diagram........................... 12 Figure 7.) Module dimensions ............................16 ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 5: Safety Instructions/Waste Disposal Rules

    The above statement from EU directive 2002/96/EC applies to all electric modules installed within EU countries. In countries outside the EU, different rules may apply regarding waste disposal of electric modules. For more information about waste disposal of your discarded equipment, contact your ELTEK VALERE INDUSTRIAL partner. ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 6: General Information

    201-005-447.00 PSC305-LV/48-10 201-005-457.00 PSC305-LV/60-8 201-005-467.00 8.0A 3.1 Main Data DC input voltage range: 18 to 75V DC input current: 22.5A @24V /11.3A @48V /9.0A @60V Nominal Output Power: 480W For more specific data, see section ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 7: Available Options And Assembly Equipment

    User Manual Page 7 (16) 3.2 Available Options and Assembly Equipment Designation Material Code DC/DC power rack DDR PSC305-LV (assembly set 19’’ sub rack 4U incl. backplane) for 202-305-607.00 six DC/DC converters PSC305 (single input/output connection for each module) Cover plate (with handle) to cover not used PSC slots, 881-MEC-BPL.03.14.B...
  • Page 8: Front View/Front Side Led Panel

    DC/DC Converter PSC305-LV User Manual Page 8 (16) 3.3 Front view/Front side LED panel The PSC305-LV is equipped with the following three LED indicators: • INPUT OK • OUTPUT OK • ALARM For more information about the LED indicators, see section 4.4.
  • Page 9: Rear Side Connection

    General alarm NC General alarm COM General alarm NO – – (+) output voltage sense link (+) DC input (-) DC input Figure 4.) Rear side connector (shown from the rear side of the module). ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 10: Cooling/Air Flow Direction

    Several modules in a system or parallel connection can be controlled and monitored through the CAN-Bus by a central DC controller unit UPC3S. Following parameters of a specific DC/DC converter unit can be controlled or monitored: • Output voltage • Output current • Module temperature • Module status ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 11: Handling

    Note: But if the module is to be removed it previously must be switched off by the input fuse! Caution : After switching off the module the internal capacitors are still fully charged. Do not touch connector pins as they can still be charged with dangerous voltage after disconnection. ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 12: Output Power Diagram

    For modules in parallel operation mode, a load balance of approximately ±10% is attained due to a sloping output voltage line (-1% at 100% Inom). The module is sustained short-circuit proof due to constant current control. Output power (example PSC305-LV/48-10) Figure 6.) Output power diagram ELTEK VALERE INDUSTRIAL ©2007...
  • Page 13: Led Indications

    The following factory-set default values are stored in PSC305 modules: 24V version 48V version 60V version Default values 24.0 48.0 60.0 Vo (V 25.2 50.4 63.0 V> (V 20.0 10.0 Iconst (A 22.8 45.6 57.0 V< (V ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 14: Maintenance

    If an external sensor lead is used for the → Check output voltage, is the connection faultless? If the unit still does not work even though all checks have been done, contact your sales agent or the ELTEK VALERE INDUSTRIAL service department. ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 15: Technical Specifications

    Operation: -20°C to +55°C; storage: -40°C to +85°C; output power derating down to 100W depending on ambient temperature and cooling Climatic conditions according to IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2 ≤1500m Max. installation altitude ≤30dBA Noise emission ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...
  • Page 16: Dimensional Drawings

    Colour (front panel) RAL 7035, black print Compliances: CE conformity Compliance to safety EN60950-1; VDE0100 T410; VDE0110; EN50178; EN60146 standards Compliance to EMC EN55011/22 class “B“; EN61000-4 T2-5 standards 7.1 Dimensional drawings: Figure 7.) Module dimensions ELTEK VALERE INDUSTRIAL ©2007 UM_PSC305LV_E_R2.0...

Table of Contents