12.3. AI-900MS Master Station Interface Card Connection

12.3.1. Master Station and AI-900MS connection

• The AI-900MS can be interfaced with up to 2 AI-MS900 master stations.
• Because up to 2 AI-900MS cards can be mounted in the AI-900MF Main Frame, up to four master stations
can be connected per frame.
• A station address must be assigned to each connected AI-MS900 station. Set the station address at each
AI-MS900 station after switching ON the power.
[Station Address Setting]
Step 1. Set the Master Station's REGISTER switch to the ON position. The "Reg_mode" indication will be
displayed on the station screen.
Step 2. Press the [XFER] key.
Step 3. According to the following table, enter the station address 1 – 4 through the use of a numeric keypad.
AI-900MS
MS/AL Slot 1
MS/AL Slot 2
Step 4. Press the [PTT] key.
Step 5. Set the REGISTER switch to the OFF position to places the station in standby mode.
Numeric keys
[0] – [9]
Line
Station Address
1
1
2
2
1
3
2
4
View A
Display panel
ABC
DEF
1
2
3
1
2
GHI
JKL
MNO
4
5
6
3
4
PRS
TUV
WXY
7
8
9
5
6
OPER
7
8
0
#
C
P T T
REDIAL
XFER
Transfer [XFER] key
Press-to-talk [PTT] key
[View
]
A
HANDSET REGISTER
Do not connect thei jack
SP. VOL.
to telephone line.
OFF ON
LINE
MINI.
MAX.
Registration ON/OFF switch
[REGISTER ON/OFF]
23