5-2. All Cooling mode (Operation of cooling only) when outside temperature is middle
(Standard: 50゜F ~ 90゜F) / Defrost mode
Oudoor header unit (MMY-MAP0726FT*-UL)
PMV1
TE1
PMV4
TE2
PMV3
SV
SV
SV5
SV
TL1
SV6
Fusible
plug
FP
SV3D
SV
Liquid tank
SV41
SV
TD1
(SV14)
SV3E
Check joint
(Liquid pipe)
PMV
TCS
SVD
SVDD
TC2 TCJ
Cooling
Outdoor unit
4-Way valve
OFF
SV4(n)
OFF(*1)
SV5
ON
SV6
Control
SV11
OFF
SV12
OFF(*2)
SV14
OFF
SV15
ON
(*1) SV4(n) of stopped compressor (n) = ON
(*2) It may be controlled.
(*3) In defrost mode, PMV4 ,PMV FS and PMV indoor also open.
The outdoor unit which communication line between indoor and outdoor is connected is the "Header unit".
Other outdoor units are called "Follower units".
Fan
FM
Fan motor
Right side
TO
Main heat exchanger
Right side sub heat exchanger
Left side
Main heat exchanger
Left side sub heat exchanger
SV15
4-way
SV11
valve
TS1
Low-pressure sensor
Check joint (High-pressure)
High-pressure sensor
TS2
Accumlator
SV2
SV
Oil
separator
SV42
SV3C
SV
TD2
TK4
Comp1
Comp2
TK1
TK2
Oil header
TK5
0
SV3A
SV3B
SV
Balance pipe
Liquid pipe
Discharge gas pipe
Suction gas pipe
PMV
TCS
SVS
SVD
SVSS
SVDD
TC1
TC2
TCJ
Cooling
SV3A
Control
Cooling thermo ON
SV3B
Control
SVD
SV3C
Control
SVS
SV3D
Control
SVDD
SV3E
ON
SVSS
PMV1
Control
PMV FS
PMV3
Close
PMV indoor
PMV4
Close(*3)
Outdoor Fan
Control
( 12 ton system described in the example of ( 6ton + 6ton ))
Outdoor follower unit (MMY-MAP0726FT*-UL)
PMV1
TE2
Check joint
TL1
(Low-pressure)
Fusible
plug
FP
Liquid tank
Fusible
plug
FP
(SV14)
Check joint
(Liquid pipe)
PMV
TCS
SVS
SVD
SVSS
SVDD
TC1
TC2
TCJ
Cooling
FS unit / Indoor unit
Cooling thermo OFF
OFF
SVD
OFF
ON
SVS
OFF
OFF
SVDD
OFF
ON
SVSS
ON
Close(*3)
PMV FS
Close(*3)
Control(*3)
PMV indoor
Close(*3)
High-pressure gas refrigerant
Condensed liquid refrigerant
Evaporative gas refrigerant (Low pressure)
− 42 −
Fan
FM
Fan motor
Right side
Main heat exchanger
Right side sub heat exchanger
Left side
Main heat exchanger
TE1
PMV4
Left side sub heat exchanger
PMV3
SV
SV11
SV
SV5
SV
SV6
Check joint (High-pressure)
High-pressure sensor
SV2
SV3D
SV
Oil
SV
separator
SV41
SV42
SV3C
SV
TD1
TD2
TK4
Comp1
Comp2
TK1
TK2
Oil header
SV3E
TK5
SV3A
SV
PMV
TCS
SVS
SVD
SVSS
SVDD
TC1
TC2 TCJ
Stop
Stop
SVD
OFF
SVS
OFF
SVDD
OFF
SVSS
ON
PMV FS
Close(*3)
PMV indoor
Close(*3)
Pressure circuit (High-pressure refrigerant)
Low-pressure circuit (Refrigerant recovery line)
TO
SV15
4-way
valve
TS1
Low-pressure sensor
Check joint
(Low-pressure)
TS2
Accumlator
Fusible
plug
SV
FP
0
SV3B
SVS
SVSS
TC1

Hide quick links: