◆ [ Set up example ]
[ 0E ] : Group setting
0 : Individual (Factory default)
1 : Group
[ 14 ] : Group Address
0: Individual
1: Header unit
2: Follower unit
[ FE ] : Branching system address (1~64)
• Should not be duplicate in one system
• Factory default : 99
[ FD ] : Priority operation mode
0 : Heating prioritized (Factory default)
1 : Cooling prioritized (The cooling is
prioritized even if setting only one unit in
one branching)
< In case of connecting one indoor unit>
Single port type FS unit
Piping
Control wiring
between indoor
unit and FS unit
(Within 49 ft (15 m))
[ 0E ] : It is not necessary to set up
[ 14 ] : It is not necessary to set up
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
Multi port type FS unit, Single port type FS unit (Long piping model)
Piping
[ 0E ] : It is not necessary to set up
[ 14 ] : It is not necessary to set up
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
Multi port type FS unit, Single port type FS unit (Long piping model)
Indoor unit
Remote
control
Indoor unit
Remote
control
Multi port type FS unit, Single port type FS unit (Long piping model)
− 100 −
<In case of connecting one group operation of
indoor units>
Single port type FS unit
Control wiring
between indoor
Remote control
unit and FS unit
(Within 49 ft
(15 m))
[ 0E ] :
1
[ 14 ] :
1
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
Remote control
[ 0E ] :
1
[ 14 ] :
1
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
<In case of connecting two group operations of
indoor units>
Single port type FS unit
Control wiring
Remote
between indoor
control
unit and FS unit
(Within 49 ft
Group control
(15 m))
[ 0E ] :
1
[ 14 ] :
1
[ FE ] :
1
[ D ] :
F
0
Remote
control
Group control
[ 0E ] :
1
[ 14 ] :
1
[ FE ] :
1
[ FD ] :
0
Piping
Indoor unit
Group control
1
1
2
2
Piping
Indoor unit
Group control
1
1
2
2
Piping
Indoor unit
Group control
1
1
1
2
1
2
1
1
1
0
0
0
Piping
Indoor unit
Group control
1
1
1
2
1
2
1
1
1
0
0
0