Selecting Installation Site - Daikin FXLQ20MHV1 Installation Manual

Vrv system inverter air conditioners
Hide thumbs Also See for FXLQ20MHV1:
Table of Contents

Advertisement

FOR THE FOLLOWING ITEMS, TAKE SPECIAL
CARE DURING CONSTRUCTION AND CHECK
AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
If not properly done, what
Items to be checked
is likely to occur
Are the indoor and
The units may drop,
outdoor unit fixed firmly?
vibrate or make noise.
Is the gas leak test
It may result in insuffcient
finished?
cooling.
Condensate water may
Is the unit fully insulated?
drip.
Does drainage flow
Condensate water may
smoothly?
drip.
Does the power supply
The unit may malfunction
voltage correspond to
or the components burn
that shown on the name
out.
plate?
The unit may malfunction
Are wiring and piping
or the components burn
correct?
out.
Is the unit safely
Dangerous at electric
grounded?
leakage.
The unit may malfunction
Is wiring size according
or the components burn
to specifications?
out.
Is something blocking
the air outlet or inlet of
It may result in
either the indoor or
insufficient cooling.
outdoor units?
Are refrigerant piping
length and additional
The refrigerant charge in
refrigerant charge noted
the system is not clear.
down?
b. Items to be checked at time of delivery
Also review the "SAFETY CONSIDERATIONS"
Items to be checked
Did you explain about operations while showing the
instruction manual to your customer?
Did you hand the instruction manual over to your
customer?
c. Points for explanation about operations
The items with
WARNING and
instruction manual are the items pertaining to possibillties for
bodily injury and material damage in addition to the general
usage of the product. Accordingly, it is necessary that you
make a full explanation about the described contents and
also ask your customers to read the instruction manual.
2-4
NOTE TO THE INSTALLER
Be sure to instruct customers how to properly operate the
unit (especially cleaning filters, operating different functions,
and adjusting the temperature) by having them carry out
operations themselves while looking at the manual.
English
Check
Check
CAUTION marks in the
3.

SELECTING INSTALLATION SITE

(1) Select an installation site where the following condi-
tions are satisfied and that meets with your customer's
approval.
• Where the floor is strong enough to dear the indoor unit
weight.
• Where the floor is not significantly inclined.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• Where sufficient clearance for installation and mainte-
nance can be ensured.
• Where optimum air distribution can be ensured.
• Where there is no risk of flammable gas leakage.
• Where piping between indoor and outdoor units is possi-
ble within the allowable limit. (Refer to the installation
manual of the outdoor unit.)
CAUTION
• Install the indoor and outdoor units, power supply wiring
and connecting wires at least 1 meter away from televi-
sions or radios in order to prevent image interference or
noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufficient enough to eliminate the noise.)
FXLQ
Window
100 or
Front side
100 or
more
more
1000 or
more
(IMPORTANT) Leave sufficient clearance for air inlet and main
tenance.
Model
FXLQ20 · 25MHV1
FXLQ32 · 40MHV1
FXLQ50MHV1
Air flow direction
1750 or
more
Air inlet
direction
Base
(length : mm)
A (mm)
B (mm)
570
1030
710
1170
990
1450
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fxlq40mhv1Fxlq25mhv1Fxlq50mhv1Fxlq32mhv1

Table of Contents