Error Decode (Profibus-Dp Extensions To En 50170); Error Code_1 (Profibus-Dp Extensions To En 50170) - Emerson STXPBS001 User Manual

Profibus network adapters
Table of Contents

Advertisement

User Manual
GFK-2746C
3.3.8

Error Decode (PROFIBUS-DP Extensions to EN 50170)

3.3.9

Error Code_1 (PROFIBUS-DP Extensions to EN 50170)

Bit
PROFIBUS Network Adapters
0~127 : Reserved
128 : DPV1
129~253 : Reserved
254 : FMS
255 : HART
7
6
5
Error Class
0xA : Application class
Error Class
0xB : Access class
Error Class
0xC : Resource class
Error Class
0xD : STXPBS001 Specific Class
4
3
2
Error code
0: Read Error
1: Write Error
2: Module Failure
3 ~7: Reserved
8: Version conflict
9: Feature not supported
10~15: User specific
Error code
0: Invalid i
1: Write length error
2: Invalid slot
3: Type conflict
4: Invalid area
5: state conflict
6: access denied
7: invalid range
8: invalid parameter
9: invalid type
10~15: User specific
Error code
0: read constrain conflict
1: Write constrain conflict
2: Resource busy
3 Resource unavailable
4 ~7: Reserved
8~15: User specific
Error code
1: Slot Parameter write error
2: Read memory error
3: Write memory error
Chapter 3