HEATING CYCLE ANALYSIS
Air
Coil
°F
COOLING CYCLE ANALYSIS
Air
Coil
°F
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x
SUPERHEAT
= SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
*Use 500 for water, 485 for antifreeze.
© 2022 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500329-01
°F
Expansion
COAX
Valve
°F
Liquid Line
°F
PSI
Water In
°F
Expansion
COAX
Valve
°F
Liquid Line
°F
PSI
Water In
TEMP. DIFF. (DEG. F) x
(DEG F)
(DEG F)
Printed in U.S.A.
Form 50PC-9SI
°F
PSI
Water Out
Look Up Pressure Drop in Waterside Pressure Drop Table
to Determine Flow Rate.
See Table 15 for Waterside Pressure Drop.
°F
PSI
Water Out
Look Up Pressure Drop in Waterside Pressure Drop Table
to Determine Flow Rate.
See Table 15 for Waterside Pressure Drop.
FLUID FACTOR* =
Pg CL-2
PSI
SaT
°F
Suction
Compressor
Discharge
PSI
SaT
°F
Suction
Compressor
Discharge