Summary of Contents for DIGITIZE System 3505 Prism LX
Page 1
System 3505 Prism LX™ Custom Interface #0080 Northeastern OnyxWorks to PrismLX Operational Notes Digitize, Inc. 158 Edison Road Lake Hopatcong, New Jersey 07849 Tel: (973) 663-1011 Part Number: 700300-0001 E-mail: info@digitize-inc.com Revision: B Website: http://www.digitize-inc.com Issue Date: 10/2021...
Page 2
Digitize, Inc. 158 Edison Road Lake Hopatcong, NJ 07849-2217 The Digitize logo (stylized) is a registered trademark of Digitize, Inc. MeshSentry and VersAlarm is a trademark of Digitize, Inc. FireTide is a trademark of FireTide, Inc. OnyxWorks® is a registered trademark of Honeywell International Inc.
Page 3
E-Mail: info@digitize-inc.com Website: http://www.digitize-inc.com This manual has been prepared by DIGITIZE, INC. for use by its licensees, distributors and customers. The information contained herein is the property of DIGITIZE, INC. and may not be copied, disclosed or reproduced, in whole or in part, without the prior written approval of DIGITIZE, INC.
Page 4
FCC NOTICE In compliance with Paragraph 15.105 of the FCC Rules and Regulations, the following notice is provided. NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
1 Introduction 1.1 Purpose The purpose of this manual is to inform the user how the OnyxWorks to Digitize PrismLX operates. The goal of the PrismLX Custom 0080 interface is to monitor the Unsupervised Printer output from the OnyxWorks CAD system and pick out the Fire Alarms and Fire Restore signals.
Introduction Digitize Inc 1.4 OnyxWorks Interface The serial data from the OnyxWorks contains a variety of signals. The PrismLX will only act on two signals. The two signals are noted below: This signal is for the activation of a Fire Alarm.
Introduction Digitize Inc 1.5 Description Field The Description field must contain a four-digit number that represents the Telegraph Box number to be queued up to be transmitted or aborted. If the box number only has one, two or three digits, they must be preceded by zeroes. The box number must be followed by the Letters FA.
2 Event Processing 2.1 Fire Alarm Activation When the OnyxWorks processes a Fire Alarm, as noted in Section #1 above, the PrismLX will process a Fire Alarm and start a 60 second countdown timer as will be note on the PrismLX color LCD display. Figure 2-1, Fire Alarm as Initiated by OnyxWorks To ACK and send the box alarm to BFD, press the Green “SEND BFD DISPATCH”.
Event Processing Digitize Inc 2.2 Fire Alarm Restore When the OnyxWorks processes a FA Restore, the PrismLX will respond as follows: 1. If a FA Restore occurs Prior to the Telegraph Box transmission, the Restore signal will auto ACK the Fire Alarm Event (if not already ACKed) and abort the countdown timer and leave the account in a restore mode waiting for the dispatcher to ACKnowledge the Restore event.
Event Processing Digitize Inc Seconds. The PrismLX will then beep every Second to alert the Dispatcher to either select to Abort, Send or do nothing to auto send the Telegraphic code to BFD. 2.4 Multiple Alarm or Restore Events 1. Should Northeastern experience several FA signals and or restores being processed in a short period of time, The Prism LX will process one at a time until the backlog is resolved.
Page 15
Event Processing Digitize Inc 3. In the thermal tape noted above, here is what occurred as reported by the OnyxWorks: a. 13:54:40 - A Fire Alarm was reported from Gainsboroug. If no other pending or active event exists, this event will print and start it sequence for a 60 second delay prior to notifying BFD as noted in section 2, Event Processing.
3 Remote Annunciator Figure 3-1, Location of Pop Up box when Alarm event is reported by the OnyxWorks to the PrismLX. Remote Annunciator pop up box indicating there is a countdown for Teleg TX to BFD. 700300-0001 Rev. B 10/21...
Remote Annunciator Digitize Inc Figure 3-2, BFD Telegraph Box Transmission is active Figure 3-3, BFD has been notified and Telegraph Box transmission ended 700300-0001 Rev. B 10/21...
Page 21
Digitize by telephone or in writing. Buyer will prepay all freight charges to return any products to the repair facility designated by Digitize and include the RMA number on the shipping container. Digitize will, at its option, either repair the defective products or parts or deliver replacements for defective products or parts on an exchange basis to Buyer, freight prepaid to the Buyer.