•
Considerations
Before troubleshooting the link, or contacting Trane Technical Support, it is helpful to have the following
information at hand.
•
•
•
•
•
•
•
•
BAS-SVX51L-EN
Two or more devices on the network with the same rotary switch address.
A valid set of prints for the project that illustrates how the devices are wired on the link (including rotary
addresses).
The type of wire used to install the devices on the link.
Whether there are BACnet
Whether the link is configured in a daisy-chain topology.
Whether there are non-Trane devices on the link.
Firmware versions loaded on controllers with an MS/TP issue.
®
Tracer
SC+ rotary switches: (valid range is 1 to 419).
Device rotary switches: (valid range is 1 to 127).
®
terminators installed at each end of the BACnet
Overview
®
link.
7