Lennox MCFA Series User Manual page 6

Mini-split system indoor unit
Table of Contents

Advertisement

On an initial call for cooling, the operation/run light is lit to signal normal operation. There will be a delay after a cooling
demand is introduced be fore unit operation begins. This delay protects the unit compressor and is normal.
When a heating demand is initiated, the opera tion light is lit to signal normal operation. The PRE-DEF indicator may
be lit as well. The indoor unit fan will not operate until the indoor coil reaches a pre-set temperature. This prevents the
delivery of cold air into the space and is nor mal.
Indoor fan is on; compressor is off
In certain normal operating modes, the indoor fan is on when the compressor is not operating.
The system turns the compressor off and leaves the indoor fan on when the indoor coil falls to a preset temperature.
This is normal operation and will prevent the indoor coil from freezing.
When the indoor fan is set for continuous opera tion, the fan continues to run when the temperat ure setting is reached
and the compressor is de-energized.
White mist comes out of the indoor unit
During cooling operation, if the indoor relative humidity is very high and the indoor unit dis charge air louvers are very
dirty, the indoor coil may freeze and a white mist (frozen vapor) may appear to come from the indoor unit. In this case,
though the unit is not in need of repair, it does need to be cleaned by a licensed pro fessional HVAC technician
(or equivalent).
During heating operation when the operation mode switches from defrost to heating, mois ture generated by the
defrost process becomes steam and may be seen as it is blown out of the indoor unit.
Sounds can be heard near the indoor unit
During certain parts of the heating or cooling pro cess, low swishing or groaning sounds may be heard near the unit as the
system pressures equal ize. This is a normal occurrence.
The table below lists possible causes and solutions to some of the most common problems. Please review this information
before calling for service.
Symptom
Unit does not start.
Indoor fan is operating; however, air is
not cool.
Unit cycles on and off frequently.
Unit not cooling properly.
Table 1. Troubleshooting
Possible Cause
Power failure
Power to unit is OFF or disconnected
Circuit breaker may be tripped or fuse may be
blown
Wireless remote control batteries may have
lost their charge or unit controller may have
malfunctioned
Temperature not properly set at con trol
Compressor may be kept off by delay
Refrigerant charge is incorrect
Air in refrigerant circuit
Compressor malfunction
Improper voltage
System refrigerant circuit is blocked
Indoor and/or outdoor coil are dirty
Air filter is dirty
Air flow around indoor and/or outdoor unit is
obstructed
Doors and/or windows are open
Direct sunlight is affecting indoor tem perature
Heat source inside is placing a large burden on
the system
Suction pressure is low due to possible refrig-
erant leak
Possible Solution
Wait for power to be restored
Turn on or reconnect power to the unit
Reset circuit breaker or replace fuse
Replace AAA size batteries in wireless remote
control. Check controller for proper function
Check temperature setting at control
Wait for delay to expire
Check for refrigerant leaks and prop erly charge
system
Evacuate and properly charge system
Check compressor and replace, if ne cessary
Check with utility company to provide proper
voltage
Clear blockage
Clean indoor and/or outdoor coil
Clean or replace air filter
Remove obstructions
Close doors and windows
Use curtains or blinds to block direct sunlight.
Reduce burden of heat source
Check for refrigerant leaks and prop erly charge
system
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mcfb seriesMfma seriesMmdb seriesMwmc series3wmc seriesM22a series ... Show all

Table of Contents