Rheem GHE119SS Use & Care Manual page 12

Commercial high efficiency water heater
Hide thumbs Also See for GHE119SS:
Table of Contents

Advertisement

Power Direct Vent
Inlet Models
GHE80SU-130(A)
or
GHE80SU-160(A)
GH80SU-200(A)
or
GHE80SU-300(A)
GHE100SU-130(A)
or
GHE100SU-160(A)
GH100SU-200(A)
or
GHE100SU-250(A)
or
GHE100SU-300(A)
GHE100SU-350(A)
or
GHE100SU-400(A)
GHE119SU-500(A)
All Models
Models GHE80SU-200(A) & GHE80SU-300(A) are limited to an altitude of 8000 ft, while all other models are limited to 8999 ft.
Model GHE119SU-500(A) if installed above 5000 ft, refer to "Gas Valve Instructions" for adjustments.
For each 90° Elbow, reduce pipe length by five (5) feet.
For each 45° Elbow, reduce pipe length by two and a half (2.5) feet.
Note: Vent pipe size should not be mixed for venting these units.
Use same diameter pipe for all venting of the unit.
Venting Configurations are the Same for SS Models:
3 inch concentric vent can only be used with 3 inch rigid piping.
4 inch concentric vent can only be used with 4 inch rigid piping.
DO NOT mismatch concentric vent terminations with different rigid piping as it may cause the heater to mal-
function or cause a lock-out condition.
DO NOT use 2 inch rigid venting with concentric vent terminations.
DO NOT use 6 inch rigid venting with concentric vent terminations.
Note: For Horizontal Power Direct Vent configurations, GHE119SS/SU models will need to have a 45 degree elbow
on the intake and a 90 degree elbow on the exhaust, if they are on the same plane.
Flexible Polypropylene pipe (ft)
Pipe Size (IN.)
Max PV
GHE80 and GHE 100 Models
GHE119-500
Models GHE80SU-200(A) & GHE80SU-300(A) are limited to an altitude of 8000 ft, while all other models are limited to 8999 ft.
NOTE: Units naturally de-rate as vent length is extended from minimum vent. De-rate also occurs when
reducing the diameter of the vent from the default size (GHE80/100 default is 3", GHE119 default is 4").
Installation
2" (5 cm)
Altitude
Range
Inlet
0-2000
20
(0 - 609 m)
(6.1 m)
2001-8999
20
(610 - 2743 m)
(6.1 m)
0-8000 ft
N/A
(0-2438 m)
0-2000
20
(0 - 609 m)
(6.1 m)
2001-8999
20
(610 - 2743 m)
(6.1 m)
0-2000
N/A
(0 - 609 m)
2001-8999
N/A
(610 - 2743 m)
0-8999 ft
N/A
(0 - 2743 m)
0-10000 ft
N/A
(0-3435 m)
5
See Below
(1.5 m)
TABLE 2. POWER DIRECT VENTING LENGTHS
3
Intake
Exhaust
0
60
N/A
N/A
Max Vent Length (Eq.Ft.)
Rigid Pipe Diameter
3" (8 cm)
Outlet
Inlet
Outlet
20
60
75
(6.1 m)
(18.3 m)
(22.9 m)
20
40
55
(6.1 m)
(12.2 m)
(16.8 m)
60
75
N/A
(18.3 m)
(22.9 m)
20
60
75
(6.1 m)
(18.3 m)
(22.9 m)
35
40
55
(10.7 m)
(12.2 m)
(16.8 m)
60
75
N/A
(18.3 m)
(22.9 m)
40
55
N/A
(12.2 m)
(16.8 m)
50
65
N/A
(15.2 m)
(19.8 m)
60
60
N/A
(18.3 m)
(18.3 m)
Min Vent Length (Eq.Ft.)
Rigid Pipe Diameter
15
5
15
(15.2 m)
(1.5 m)
(15.2 m)
4
Intake
Exhaust
0
60
0
80
12
4" (10 cm)
6" (15 cm)
Inlet
Outlet
Inlet
120
135
N/A
(36.6 m)
(41.1 m)
120
135
N/A
(36.6 m)
(41.1 m)
120
135
120
(36.6 m)
(41.1 m)
(36.6 m)
120
135
N/A
(36.6 m)
(41.1 m)
120
135
N/A
(36.6 m)
(41.1 m)
120
135
N/A
(36.6 m)
(41.1 m)
120
135
120
(36.6 m)
(41.1 m)
(36.6 m)
70
85
120
(21.4 m)
(25.9 m)
(36.6 m)
120
130
120
(36.6 m)
(39.6 m)
(36.6 m)
5
15
5
(1.5 m)
(15.2 m)
(1.5 m)
Outlet
N/A
N/A
135
(41.1 m)
N/A
N/A
N/A
135
(41.1 m)
135
(41.1 m)
130
(39.6 m)
15
(15.2 m