Liquid Cooling Specifications - Gigabyte H263-S63-LAN1 User Manual

Hpc server – 4th gen. intel xeon scalable server dp 8 x gen4 nvme/sata/sas hci & hybrid/private cloud server
Table of Contents

Advertisement

3-4-1 Liquid Cooling Specifications

The cold plate assembly in the liquid cooling assembly mounts directly on top of the processors.
The retention mechanism for installation on top of the processors is integrated into the cold plate. The liquid
coolant contained within the tubes, is a mixture of demineralized water and propylene glycol with the following
beneficial features: Anti-Freeze, Anti-Corrosion and Anti Bacterial. The following table lists the features and
specifications of the liquid cooling assembly.
Cold plate material
Thermal Interface Material
Operating liquid temperature
Operating Air temperature
Coolant Flow Rate
Operating Humidity
Storage Temperature
Storage Humidity
Height
Weight
NOTE: In the event that the room's relative humidity exceeds 60% then the inlet water temperature
must be set between 40° to 45°C to avoid condensation and to keep the system running optimally.
Specification
System Hardware Installation
Copper
Dowsil TC-5622
Minimum: 2°C
Maximum: 65°C
40°C
0.75 - 1.4 l/min (per node)
5 - 95%
-40°C to 70°C
5 - 95%
Dimensions
24.01 mm
1.87 lbs (848g per node)