Fujitsu Airstage AJ 040LCLDH Series Installation Manual page 13

Outdoor unit
Hide thumbs Also See for Airstage AJ 040LCLDH Series:
Table of Contents

Advertisement

Level 1
Low noise mode
Level 2
level setting
42
Prohibited
Level 1: The operating sound lowers from the rated value
Level 2: The operating sound lowers from the Level 1
Enable
Disable
Intelligent refriger-
Enable only evaporation
53
ant control
temperature control
Enable only condensation
temperature control
60
Prohibited (Factory default)
61
Prohibited (Factory default)
Setting number (x00)
Setting number (x01)
Electricity meter
No. setting 1 (*2)
70
Setting number (x98)
Setting number (x99)
Set the ones digit and tens digit of the No. of the electricity meter connected to CN135.
Setting number (0xx)
Electricity meter
Setting number (1xx)
No. setting 2 (*2)
71
Setting number (2xx)
Set the hundreds digit of the No. of the electricity meter connected to CN135.
Setting number (xx00)
Setting number (xx01)
Electricity meter
pulse setting 1
(*3)
72
Setting number (xx98)
Setting number (xx99)
Set the ones digit and tens digit of the No. of the electricity meter pulse setting con-
nected to CN135.
Setting number (00xx)
Setting number (01xx)
Electricity meter
pulse setting 2
(*3)
73
Setting number (98xx)
Setting number (99xx)
Set the hundreds digit and thousands digit of the electricity meter pulse setting con-
nected to CN135.
90
Prohibited (Factory default)
*1: Do not set this for outdoor units with subordinate setting.
*2: When electricity meter No. is set to "000" and "201 to 299", the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to "0000", the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
0
0
4
2
0
1
0
2
0
0
0
1
5
3
0
2
0
3
6
0
0
0
6
1
0
0
0
0
0
1
7
0
···
···
9
8
9
9
0
0
7
1
0
1
0
2
0
0
0
1
7
2
···
···
9
8
9
9
0
0
0
1
7
3
···
···
9
8
9
9
9
0
0
0
(1) Turn on the power of the outdoor unit and enter standby mode.
• When system is normal
POWER/MODE lamp lights up.
(ERROR lamp is off.)
POWER/MODE
POWER
ERROR
MODE
lamp: ON
LED101
LED102
(GREEN)
(RED)
7-segment
LED105
LED104
display:
turn off
MODE
SELECT
ENTER
/EXIT
MODE/EXIT
SW107
SW108
SW109
button
SELECT button
(2) Setting method
Use the "MODE/EXIT", "SELECT",
and "ENTER" buttons to configure
settings according to the proce-
dures below.
(If no setting is made, the factory
default setting will be displayed.)
1: Function setting
First 2 digits Last 2 digits
2: Setting the first
2 digits
Every press of the
"SELECT" button will
change the setting
number for the first 2
digits.
EXIT: Press the "MODE/EXIT" button to cancel the setting mode.
• When system is error
Check the settings as there is an error in the
settings for outdoor unit address
(DIP switch SET 3-1, 2) or number of con-
ERROR
nected subordinate units (DIP switch SET
lamp: OFF
3-3, 4).
POWER/MODE
POWER
MODE
lamp: ON
LED101
(GREEN)
LED105
ENTER
7-segment
button
display:
MODE
SELECT
"-" display
/EXIT
SW107
SW108
: Press the "MODE/EXIT" button
: Press the "SELECT" button
: Press the "ENTER" button.
: Press the "ENTER" button for
more than 3 seconds.
7-segment LED display (LED 105, LED 104)
(When [F3] to [F9] are displayed, continue to press
the "SELECT" button until [F2] is displayed.)
(Flashing)
3: Setting the last 2 digits
Continue to press the "SELECT" button until the
desired number appears at the last 2 digits.
Setting is complete when the lamp lights up
Press "ENTER" button to return to "2: Setting the
first 2 digits" (If there is no operation for 5 seconds
after the setting, the display will return to "2: Setting
the first 2 digits".)
(Continue to press the "SE-
LECT" button until the desired
number appears at the last 2
digits.)
Setting is complete when the lamp lights up
Press "ENTER" button to return to "2: Setting the
first 2 digits" (If there is no operation for 5 seconds
after the setting, the display will return to "2: Setting
the first 2 digits".)
ERROR
ERROR lamp:
Blinking
LED102
(RED)
LED104
ENTER
SW109
En-12