OCEM IRM Operation And Maintenance Manual

Insulation resistance measurement

Advertisement

Quick Links

06ea44df-4930-4943-9da8-a9181f2c00fe
Operation and Maintenance Manual
Insulation
Resistance
Measurement
INSULATION RESISTANCE
MEASUREMENT
SERIES CIRCUITS 6.6A
UP TO 30 KVA
FIELDBUS CONNECTION
LONWORKS
MANAGEMENT SOFTWARE
SERVER AND CLIENT
ocem
EN

Advertisement

Table of Contents
loading

Summary of Contents for OCEM IRM

  • Page 1 06ea44df-4930-4943-9da8-a9181f2c00fe Operation and Maintenance Manual Insulation Resistance Measurement INSULATION RESISTANCE MEASUREMENT SERIES CIRCUITS 6.6A UP TO 30 KVA FIELDBUS CONNECTION LONWORKS MANAGEMENT SOFTWARE SERVER AND CLIENT ocem...
  • Page 2 Contact us OCEM AT +39 051 66 56 611 info@ocem.com Editions Release Date Notes 14/12/2020 First emission 03/02/2021 Content review 22/04/2021 Content review UT-MT-0930_1.3_22-04-2021 (EN) | | These specifications may be subject to change. © Copyright 2020 Energy Technology S.r.L. (Italy) | All rights reserved.
  • Page 3: Table Of Contents

    GENERAL INFORMATION Package content Manual reference guide Safety instructions Safety symbols 1.5 Definition of operator Limited warranty CE marking 1.8 Confidentiality, industrial property rights Disposal 1.10 Article identification DESCRIPTION OF THE DEVICE 2.1 General characteristics Article number INSTALLATION Insulation measurement device 3.2 Installation of the device IRMS remote control 3.4 Ethernet connection ADJUSTMENTS AND MAINTENANCE Preliminary operations...
  • Page 4 Page left intentionally blank UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 5: General Information

    GENERAL INFORMATION Package content The IRM of Energy Technology S.r.L. is a measurement device designed for the monitoring of the insulation resistance on a circuit airport series. The device is designed in compliance with: ● IEC: 61010‑1 Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use. The measurement can be performed on a series circuit powered by a regulator unit compliant with: ● IEC 61822: Electrical installations for lighting and signalling in aerodromes ‑ Constant current regulator ● FAA AC 150/5345‑10: L‑828 Constant current regulator unit without monitoring; L‑829 Constant current regulator unit with monitoring ●...
  • Page 6: Manual Reference Guide

    Manual reference guide This document contains all the information related to the equipment and describes the procedures to follow during the installation of the product and during ordinary maintenance. The document is indented for all operators that must intervene on the equipment. The precautions provided in the manual are always preceded by a symbol as illustrated below: Indicates the warnings, the notes, the suggestions and other points on which is intended to draw the attention of the reader. Indicates the operations to be carried out mandatorily or the informations which should be carefully watched to avoid possible risks.
  • Page 7: Safety Symbols

    Safety symbols The symbols illustrated in the following table are used in the user and maintenance manual and on the device. These symbols serve to indicate the existence of any dangerous situations, to indicate provisions and prohibitions in relation to the situations that may represent an hazard for the operator or indicate the behaviour to adopt to minimize the risk for the operator. Warning signs Prohibition and obligation signs W001 | General warning sign P001 | General prohibition sign W004 | Laser beam M001 | General mandatory sign M002 | Refer to instruction manual/ W005 | Non-ionizing radiation booklet M005 | Connect an earth terminal to the W006 | Magnetic field ground W012 | Electricity M009 | Wear protective gloves...
  • Page 8: Limited Warranty

    Limited warranty Energy Technology S.r.L. assures that all the IRM products marketed are free of manufacturing defects at the time of shipment. This limited warranty will be valid for the period indicated in the sales agreement. THIS LIMITED WARRANTY IMMEDIATELY DECAYS IF THE PRODUCT IS USED FOR PURPOSES OTHER THAN ORIGINALLY INTENDED. This limited warranty is provided by Energy Technology S.r.L. to the original purchaser of IRM products as identified by the documents issued at the time of purchase. This limited warranty can be transferred to the subsequent purchasers of the Product, only on condition that this Product is resold as NEW and with the original packaging. Each change and/or tampering made to the product immediately ends of the warranty. Energy Technology S.r.L. cannot be held responsible for any damage to items or persons deriving...
  • Page 9: Ce Marking

    CE marking This equipment complies with the requirements of European legislation for the CE marking. The user should carefully read this document and respect all the requirements quoted. This equipment meet the requirements in relation to health and safety of the main EC directives, and in particular of the EMC Directive on electromagnetic compatibility (2014/30/Ue)and of the LV Directive relating to electrical equipment designed for use within certain voltage limits (2014/35/UE). Confidentiality, industrial property rights The Customer needs to adopt the maximum confidentiality with respect to all the information of technical nature (including, by way of example and not exhaustively, plans, programmes, documentation, formulas, recipes, setting and correspondence) received by the Supplier or in any case assimilated or gained during the conclusion of the Contract of sale. Any right regarding intellectual and industrial property connected to equipments and to any other element included in the supplied Goods as indicated in the Contract remain exclusive property of the Supplier. Disposal At the end of use, the user must confer all the waste in suitable differentiated waste collection centres. It is the responsibility of the user the correct disposal of the equipment in accordance with the WEEE Directive and with the respective national laws in force at the time of disposal. These equipments must never be disposed of in the household waste. 1.10 Article identification On the equipments there is an identification plate of the article, where is reported the article code; on the plate there are additional data: the name of the model, employments or use, power supply features, any trademarks and/or marks that attest the agreement of the equipment to specific regulations or legislations. UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 10 Page left intentionally blank UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 11: Description Of The Device

    IRM is compliant with the rule IEC (61010-1) The device IRM described in this manual has been designed to be installed on L-828 or L-829 series circuit powered by regulator units compliant with FAA AC150/5345-10. Each series circuit to be monitored must be associated with a device IRM, installable in the cabin.
  • Page 12 2.1.1 Generality The device IRM performs measure of the insulation resistance of the circuit airport series through the periodic application of a voltage of about 800 V to an end of the series circuit by measuring the leakage current to the ground. The measuring interval can be customised (default: 60 sec). The device IRM can be inserted on the series circuit independently on the type of regulator unit and without the need to make changes to the circuit. A disconnector switch easily accessible allow the supply control. A LED display positioned on the front of the device IRM allows to locally view the measured insulation resistance value AND alternatively the current values (and voltage, optional) on the series circuit, and the main alarms. All the threshold values (pre‑alarm and alarm) can be customised. The internal connection between the measurement card and the interface card is realized through a pair of optical fibres. The device IRM allows the remote monitoring (optional) of the measured values. The device is suitable at monitoring series circuits powered by power regulator units not higher than 30 kVA/6.6 A, in the measuring field 10 kΩ ÷ 500 MΩ. 2.1.2 Construction detail The device consists of a case in zinc‑coated steel, painted with thermosetting epoxy powders (colour RAL 7032).
  • Page 13: Article Number

    Article number IRM -1-1-RC-0-B example: Infeed Cut-Out: 1 = Cut-Out present Voltage measuring on the series circuit = Voltage on the series circuit not detectable = TV for voltage measuring on the series circuit Electromechanical remote signalling (NO/NC): = No remote signalling = Remote signalling with terminal board = Remote signalling with connector Voltage loop: = Voltage loop not present = Voltage loop present...
  • Page 14 Page left intentionally blank UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 15: Installation

    IEC 61822 Electrical installations for lighting and signalling in aerodromes - Constant current regulator • FAA AC 150/5345‑10 Specification for Constant Current Regulators and Regulator Monitors; • ICAO Annex 14. Series circuit Series circuit not monitored monitored by IRM UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 16: Installation Of The Device

    Installation of the device Store the device in its original packaging until the time of installation. Check the supply features before installing the device. Use the device only in combination with series circuit powered by CCR regulator units by power not higher than 30 kVA, compliant with the standard IEC 61822, FAA AC 150/5345‑10 (L‑828, L‑829) and ICAO Annex 14. Before proceeding with the operation, check the conditions of the device: ● check that the mechanical fixing of the components are steady; ● check that the internal connections are properly configured;...
  • Page 17 PROTECTIVE CONDUCTOR (min. 10mm SERIES CIRCUIT max 6.6A ‑ 30kVA UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 18 REMOTE SIGNALLING UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 19 REMOTE SIGNALLING UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 20: Irms Remote Control

    IRMS remote control The IRMS software allows the supervision of the system of meters with CNT interface LONTALK type. The measurement devices IRM -_-_-__-_-A are equipped with the LonTalk network interface. The supervision software must be installed on a PC connected through router to the fieldbus LonTalk to communicate with the measurement devices IRM. Through Ethernet connection it interfaces with the LAN.
  • Page 21: Ethernet Connection

    Ethernet connection The meters with CNT interface ETHERNET type may be interfaced directly with the network structure. The IRM -_-_-__-_-B measurement devices are equipped with ETHERNET network interface and may be configured with an own IP address to be easily reached on the existing LAN data network. The supervision server of the whole system directly reach the devices and can collect data and log from the units. UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 22 Page left intentionally blank UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 23: Adjustments And Maintenance

    ADJUSTMENTS AND MAINTENANCE After completing the installation, close the device with the key. Only now is possible to close the upstream cut-out to supply the device. Preliminary operations If the device is equipped with a local cut-out, rotate it in ON position. When the device is ONLINE (series circuit powered) the system periodically performs the measure of the leakage current: the meter applies a voltage of about 800 V to an end of the series circuit by measuring the leakage...
  • Page 24: Visualization Current Value (And Voltage - Optional)

    Visualization current value (and voltage - optional) The device can monitor the actual current value on the connected series circuit. If the device is equipped with the voltage measurement device (optional) is possible to monitor also the actual voltage value on the connected series circuit. UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 25: Parameter Management

    Parameter management The device is provided already configured with the default values. All the parameters can be freely customised on the basis of the customer needs. The configurable parameters are the following: ● pre‑alarm threshold; ● alarm threshold; ● measuring interval UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 26 4.3.1 Pre-alarm threshold Pre‑alarm limit value (default value: 1.00 MΩ). If the resistance value if the insulation value falls below the set threshold, the WARNING signal activates. The overcoming of the threshold is locally signalled by turning on the LED WARNING (yellow). The same information is transferred to the supervisor through the data connection. If present, the remote signalling system (optional) activates the relay by exchanging the status of the respective contacts NO-NC.
  • Page 27 4.3.2 Alarm threshold Alarm limit value (default value: 0.20 MΩ). If the resistance value if the insulation value falls below the set threshold, the ALARM signal activates. The overcoming of the threshold is locally signalled by turning on the LED ALARM (red). The same information is transferred to the supervisor through the data connection. If present, the remote signalling system (optional) activates the relay by exchanging the status of the respective contacts NO-NC.
  • Page 28 4.3.3 Measuring interval The operator can customise the interval of time between one measure of the insulation resistance and the subsequent one (default: 60 s). UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...
  • Page 29: Scheduled Maintenance

    Wait for the discharging time (at least 5 min) and check using appropriate instruments that there are no residual energies before accessing the electrical equipment. To minimize operations, always pay the greatest attention to handling and storage of devices and carry out installation procedures with extreme precision. In accordance with the suggestions contained in the document ICAO Airport Service Manual ‑ Part 9: Airport Maintenance Practices, or on the basis of what reported in the document FAA AC 150 5340‑30, the devices IRM must be subjected to regular maintenance. In order to assure the proper functioning and the maximum duration of the operating lifetime of the device all the checks and periodical audits must be carried out and, if necessary, the necessary corrective procedures must be activated to restore and ensure operative safety levels foreseen by the standards.
  • Page 30: Spare Parts

    Spare parts Always check the version of the device installed and the accessories present. Description Code Article Auxiliary fuses 5x20 ‑ 1A Delayed 487.0015 Interface/display card (F077) ‑ version with relay SESMC0004 Interface/display card (F077) ‑ base version (without relay) 150.3794 Measurement card (F058) 150.2876 Main cut-out CESZR0005 Control lever cut‑out + shaft CE1ZA0003+CE1ZL0004 Auxiliary transformer 230V/400V (17‑0‑17V) 100.1395 Auxiliary transformer 230V/9V 100.1396 Amperometric Transformer 100.1248 Voltmetric Transformer 100.1397 UT-MT-0930_1.3_220421 (EN) Operation and Maintenance Manual...