Parameter Overview
The 2 main settings on the unit are the Set Point and the Difference Parameters.
Set Point: indicates what midway humidity level the unit is to achieve.
Difference: The point away from the Set Point that the Output Relay should start or stop operating.
The difference value is the top and bottom range that you wish the unit to try and maintain. Using the following
settings of Set Point = 50% and Difference = 5% the following happens.
Humidifying Mode: the relay turns on when at or below 50% (Set Point) and turns off when at or above 55%
Dehumidify Mode: the relay turns on when at or above 50% (Set Point) and turns off when at or below 45%
The main settings can be checked at any time: In normal mode, press the UP key to display Humidity Set
Point or press the DOWN key to display the Difference setting.
Parameter Menu and Settings
Code
F1
F2
F3
F4
F5
F6
F7
F8
B1
B2
K1
K2
Parameter Settings can be changed in one of three different Menus. The User and Admin Menus are used to
adjust the main parameter settings marked with an F.
User Menu: Press and hold the SET key for about 3 seconds until the display changes. This allows
changes to the Parameters F1 & F2 only. Helpful if you are only making minor adjustments.
Admin Menu: Press and hold SET and UP keys together for about 3 seconds until the display
changes. This allows changes to the Parameters F1 to F8.
The Sensor Menu is only used to coordinate the sensor attributes with the DHC-100+ unit. These settings are
marked as B1, B2, K1 & K2. Each DHC-100+ unit is pre set with the sensor that has been attached to it as
each sensors attributes are individual to that sensor. This makes for a more accurate reading and allows users
to replace the sensor with another compatible type in the future but still allow the DHC-100+ to remain
accurate.
Sensor Menu: Press and hold the set key for 10 seconds This changes the Parameters B1 to K2
Operating Instructions
Description
Set Point
Difference
Time delay
Alarm
Operate ON When Error
Operate OFF When Error
Calibration
Mode Selection
Zero Offset
Slope
Default
Range
50%
10% to 99%
5%
1 to 50%
0 minute
0 to 99 min
0 %
0 to 50%
10 minute
0 to 99 min
50 minute
0 to 99 min
0%
+ or – 15%
0= Humidify
0
1= Dehumidify
5000 - 9999
Pre-set
2000 - 3999