Quick Start Guide
Step 11 - Configure Controller (continued)
Alarm Relay Jumpers and 1-Wire Data reference
Jumpers are located on the top of the controller.
Alarm Relay Jumper Factory Defaults are Open On Alarm
1-Wire Reference Factory Default is -48V.
Step 12 - Controller Basic Operation
Controller Alarm Status: The display changes colors; Green = Normal, Amber = Minor Alarm, Red = Critical/Major
Alarm
Some alarms may occur during initial installation; example: thermal probe fail or Major/Minor communication
fail.
Clear these alarms: Via Controller Display: follow the menu path; Menu > Control/Operation > Clear Events or
Uninstall Equipment.
Via web pages or EasyView2; Select the Maintenance tab > clear latched events and clear
missing devices.
Verify Basic Installation Settings: Date, Time, Battery Type, number of strings and float voltage
Controller Display - Menu > Configuration > System Settings and Menu > Configuration > Batteries.
Web pages or EasyView2 - Installation Tab for Date, Time. Site ID and Site Description
Settings Tab > Battery Management for Battery
Type and number of battery strings installed