Haier GE NF96DV Installation Instructions Manual page 39

Warm air gas furnace
Hide thumbs Also See for GE NF96DV:
Table of Contents

Advertisement

Connect the desired speed tap to the "EAC" terminal and
the neutral tap to the neutral terminal on the ignition control
(refer to the furnace wiring diagram). The ignition control
will control the motor's operation, including a nominal 20
second "on" delay with a call for heat and a nominal 180
second "off" delay when the thermostat is satisfied. It will
also operate the motor on a call for cooling, with no "on" or
"off" delays.
Verify that the unit is operating at the desired speed and
within the rise range as shown on the unit rating plate.
The correct replacement motor must be installed as soon
as possible to ensure continued satisfactory operation of
the furnace.
Control Diagnostics
Troubleshooting
Make the following visual checks before troubleshooting:
1. Check to see that the power to the furnace and the
integrated ignition/blower control board is ON.
2.
The manual shutoff valves in the gas line to the furnace
must be open.
3.
Make sure all wiring connections are secure.
4.
Review the Sequence of Operation.
Start the system by setting thermostat above room
temperature. Observe system response. Then use the
information provided in this section to check the system
operation.
The furnace has a built-in, self-diagnostic capability. If a
system problem occurs, a fault code is shown by a red LED
on the control board. The control continuously monitors its
own operation and the operation of the system. If a failure
occurs, the LED will indicate the failure code. The flash
codes are presented in Table 12.
Fault Code History Button
The control stores the last five fault codes in memory. A
push button switch is located on the control. When the
push button switch is pressed and released, the control
flashes the stored fault codes. The most recent fault code
is flashed first; the oldest fault code is flashed last. To
clear the fault code history, press and hold the push button
switch in for more than 5 seconds before releasing.
High Heat State LED
On models, a green LED is provided on the control board
to indicate high heat state (see Table 13).
507962-01G / 31-5000654
CFM LED
On models equipped with a variable speed motor, an amber
LED is provided on the control board to display CFM. To
determine what CFM the motor is delivering at any time,
count the number of times the amber LED flashes. Each
flash signifies 100 CFM; count the flashes and multiply by
100 to determine the actual CFM delivered (for example:
10 flashes x 100 = 1000 CFM).
LED Status
LED Off
LED On
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
Table 12. Failure Codes - Red LED
LED Status
LED Off
LED On
LED Flashing
Table 13. High Heat State - Green LED
Issue 2149
Fault Description
No power to control or control
hardware fault detected
Normal operation
Flame present with gas valve off
Pressure switch closed with inducer off
Low-fire pressure, rollout, or aux limit
switch open
High limit switch open
Not used
Pressure switch cycle lockout
Lockout due to no ignition
Lockout due to too many flame
dropouts
Incorrect polarity and phasing
Description
No demand for high heat
High heat demand, operating normally
High heat demand, high pressure
switch not closed
Page 39 of 51

Advertisement

Table of Contents
loading

Table of Contents