Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 45

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Ferrule
The following table shows wire ferrules and its associated tools compatible with the terminal block.
The shape of the wire ferrule differs depending on the crimp tool to be used, use the reference product.
If the product other than referenced products is used, the wire ferrule cannot be removed. Sufficiently confirm that the wire
ferrule can be removed before use.
<Reference product>
Manufacturer
PHOENIX CONTACT GmbH & Co. KG
The wires to connect the spring clamp terminal block are described below.
No. of wire per terminal
Single wiring
■Wire end treatment
Strip the cable about 10 mm from the tip to connect a wire ferrule at the stripped area.
Failure to do so may result in electric shock due to the conductive part.
If the wire strip length is too short, it may result in the poor contact to the spring clamp terminal part.
Depending on the thickness of the sheath, it may be difficult to insert into the insulation sleeve, so select the wires by referring
to the appearance diagram.
Strand wire/single wire
10mm
Check the shape of the wire insertion opening with the following chart, and use the smaller wire ferrule than the described
size.
Also, insert the wire with care so that the wire ferrule is in proper orientation.
Failure to do so may cause the bite of the terminal and the damage of the terminal block.
Shape of the wire
insertion opening
2.4mm
1.5mm
Terminal block
Sleeve
Ferrules with insulation sleeve
Ferrules without insulation sleeve
Wire size
Single wire, strand wire
AWG 24 to 16
(0.2 to 1.5)
Sectional shape of a wire ferrule
When using a tool of the reference
product, the sectional shape becomes
a trapezoid close to a rectangle.
Ferrules model
Suitable wiring size
AI 0.25-8 YE
0.25
AI 0.34-8 TQ
0.3, 0.34
AI 0.5-8 WH
0.5
AI 0.75-8 GY
0.75
A 0.25-7
0.25
A 0.34-7
0.3, 0.34
A 0.5-8
0.5
A 0.75-8
0.75
AI 1.0-8
1.0
AI 1.5-7
1.25, 1.5
Ferrule with insulation sleeve
AWG 23 to 19
(0.25 to 0.75)
Ferrule with insulation sleeve
Insulation sleeve
2 to 2.8 mm
14 mm
Crimp tool
CRIMPFOX 6
Ferrule without insulation
sleeve
AWG 23 to 16
(0.25 to 1.5)
Contact area
(Crimp area)
8 mm
6 WIRING