KEPCO RA 19-4C Quick Start Manual

Rack adapter
Hide thumbs Also See for RA 19-4C:

Advertisement

Q U I C K S T A R T G U I D E
KEPCO
I — INTRODUCTION
SCOPE OF MANUAL. This Quick Start Guide covers
installation and operation of the Kepco RA 19-4C Rack
Adapter for two common configurations. For the full capa-
bilities and specifications of the RA 19-4C and to take
advantage of the many choices and features not covered in
this Quick Start Guide, the user is urged to download the
complete Operator's Manual from the Kepco web site at
www.kepcopower.com/support/opmanls.htm#ra19-4c.
DESCRIPTION. Kepco RA 19-4C rack adapters are
specifically designed for up to four 300W, 600W, 1200W/
1500W HSF power supplies, both with -A suffix and older
legacy models (non-A suffix).
II — PRE-INSTALLATION
NOTE: Either local or remote sensing MUST
be used except for HSF 1200W/1500W
(legacy non -A suffix) models.
DIP SWITCHES. The DIP switches (Figure 1) are
arranged as follows: DIP 1 is for PS1 sense lines; DIP 2 is
for PS2 sense lines and for paralleling PS1 and PS2. DIP 3
is for PS3 sense lines and for paralleling PS2 and PS3. DIP
4 is for PS4 sense lines and for paralleling PS3 and PS4.
Table 1 describes the function of each DIP switch position.
KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000  FAX (718) 767-1102
©2022, KEPCO, INC
Data subject to change without notice
An ISO 9001 Company.
RA 19-4C
RACK ADAPTER
FIGURE 1. REAR PANEL CONNECTIONS, TYPICAL FOR EACH SLOT
www.kepcopower.com   email: hq@kepcopower.com
The rack adapter is user-configurable for parallel, series, or
independent power supply operation. Forced current shar-
ing and OR'ing diodes for N+1 redundancy are built into the
HSF power supplies. Redundant a-c inputs are provided to
deliver independent source power to each power supply in
a redundant pair. User-configurable keying can ensure that
only the correct power supply can be installed in a keyed
slot. Input/output connections between RA 19-4C and HSF
power supply are via HSF connectors that plug into corre-
sponding connectors of the RA 19-4C. All connections are
made at the rear panel (see Figure 1).
INDEPENDENT OPERATION. The RA 19-4C rack
adapter is shipped with the DIP switches of all slots config-
ured for independent operation (see Figure 1) and local
sensing.
PARALLEL OPERATION. The most common use for
the RA 19-4C rack adapter is with two or more identical
HSF modules adjusted to the desired output voltage, con-
nected in parallel to a single load with forced current shar-
ing to increase current output, increase reliability and/or
provide redundancy. Only adjacent slots can be connected
in parallel using DIP switches.
228-1671 REV 2
RA 19-4C
Rack Adapter
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RA 19-4C and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for KEPCO RA 19-4C

  • Page 1 Table 1 describes the function of each DIP switch position. in parallel using DIP switches. KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000  FAX (718) 767-1102 www.kepcopower.com   email: hq@kepcopower.com ©2022, KEPCO, INC...
  • Page 2 7. Set position 10 to ON. This connects the common lines bus (CB) for slots 4 and 3. (-COM) for slots 4 and 3. KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000  FAX (718) 767-1102 http://www.kepcopower.com   email: hq@kepcopower.com 228-1671 REV 2...
  • Page 3 Operator Manual for keeping the weight of the input, output and signal cables. KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000  FAX (718) 767-1102 http://www.kepcopower.com   email: hq@kepcopower.com 110122 228-1671 REV 2...
  • Page 4 • Terminal G (Ground) is the safety ground con- wires must be twisted and/or shielded. nection for the RA 19-4C. KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000  FAX (718) 767-1102 http://www.kepcopower.com   email: hq@kepcopower.com 228-1671 REV 2...